Procedure
1. To find the
Keypad control
menu, scroll down in the main menu until the location indication
M3
shows on the first line of the
display.
READY
STOP
I/O term
P1
P4
e
3
0
b
g
0
3
3
.1
0
Keypad control
2. To go to the
Keypad control
menu from the main menu, push the Menu button Right.
8.4.2 Keypad Control Parameters M3
Table 11: Keypad Control Parameters, M3
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P3.1
Control place
1
3
1
125
The control mode
1 = I/0 terminal
2 = Keypad (control panel)
3 = Fieldbus
R3.2
Keypad reference
P2.1.1
P2.1.2
Hz
0.00
123
0 = Forward
1 = Reverse
P3.3
Direction (on keypad)
0
1
0
P3.4
Stop button
0
1
1
114
0 = Limited function of Stop button
1 = Stop button always enabled
8.4.3 Changing the Control Mode
Context:
3 control modes are available to control the AC drive. For each control place, a different symbol shows on the display:
The control mode
The symbol
I/O terminals
I/O term
Keypad (control panel)
Keypad
Fieldbus
Bus/Comm
Using the Control Panel
Operating Guide | VACON® NXI Inverters FI9-FI14
AQ304441431479en-000101 / DPD00909| 61
Danfoss A/S © 2019.11