Enclosure size
Type
I
L
[A]
Bussman aR fuse type
Fuse size
Fuse U
n
[V]
Fuse I
n
[A]
Number of fuses
FI12
NXI_0460 6
460
170M6305
3SHT
1250
700
4
NXI_0502 6
502
170M6305
3SHT
1250
700
4
NXI_0590 6
590
170M6305
3SHT
1250
700
4
NXI_0650 6
650
170M6277
3SHT
1100
1000
4
NXI_0750 6
750
170M6277
3SHT
1100
1000
4
NXI_0820 6
820
170M6277
3SHT
1100
1000
4
FI13
NXI_0920 6
920
170M6305
3SHT
1250
700
6
NXI_1030 6
1030
170M6277
3SHT
1100
1000
6
NXI_1180 6
1180
170M6277
3SHT
1100
1000
6
FI14
NXI_1500 6
1500
170M6305
3SHT
1250
700
2 × 6
NXI_1900 6
1900
170M6277
3SHT
1100
1000
2 × 6
NXI_2250 6
2250
170M6277
3SHT
1100
1000
2 × 6
12.4.5 Cable Sizes for 640–1100 V DC (525–690 V AC)
Table 22: Cable Sizes for 640–1100 V DC (525–690 V AC)
Enclosure size
(1)
Drive type
I
L
[A]
Supply cable Cu [mm
2
]
Motor cable [mm
2
]
(2)
FI9
NXI_0125 6
125
2×(1×24)
(3)
Cu: 3×95+50
Al: 3×120+70
NXI_0144 6
144
2×(1×24)
(3)
Cu: 3×95+50
Al: 3×120+70
NXI_0170 6
170
2×(1×24)
(3)
Cu: 3×95+50
Al: 3×120+70
NXI_0208 6
208
2×(1×24)
(3)
Cu: 3×150+70
Al: 3×240Al+72Cu
FI10
NXI_0261 6
261
3×(1×24)
(3)
Cu: 3×185+95
Al: 2×(3×95Al+29Cu)
NXI_0325 6
325
5×40
(4)
Cu: 2×(3×95+50)
Al: 2×(3×150Al+41Cu)
NXI_0385 6
385
5×40
(4)
Cu: 2×(3×120+70)
Al: 2×(3×185Al+57Cu)
NXI_0416 6
416
5×40
(4)
Cu: 2×(3×150+70)
Al: 2×(3×185Al+57Cu)
Specifications
Operating Guide | VACON® NXI Inverters FI9-FI14
AQ304441431479en-000101 / DPD00909
120 | Danfoss A/S © 2019.11
Summary of Contents for VACON NXP FI10
Page 1: ...Operating Guide VACON NXI Inverters FI9 FI14...
Page 2: ......