Procedure
1. Remove the external Start signal before resetting the fault to prevent that the drive starts again without a note.
2. There are 2 options to reset a fault:
- Push the [reset] button on the control panel for 2 s.
- Use a reset signal from the I/O terminal or fieldbus.
The display goes back to the same state it was before the fault.
11.3 Creating Service Info File
Context:
Use these instructions to create a service info file in VACON
®
NCDrive PC tool to help to troubleshoot in a fault situation.
Prerequisites:
Make sure the VACON
®
NCDrive PC tool is installed on the computer. To install it, go to our website
.
Procedure
1. Open the VACON
®
NCDrive.
2. Go to
File
and select
Service Info...
.
The service information file opens.
3. Save the service info file on the computer.
Fault Tracing
Operating Guide | VACON® NXI Inverters FI9-FI14
AQ304441431479en-000101 / DPD00909
94 | Danfoss A/S © 2019.11