Frame sizes E and F
60
º
AVM - Pulse Width Modulation, 380–500 V
Figure 4.30: Derating of I
out
for different T
AMB, MAX
for frame
sizes E and F at 500 V, using 60
º
AVM in High torque mode
(160% over torque)
SFAVM - Stator Frequency Asyncron Vector Modulation, 380–
500 V
Figure 4.31: Derating of I
out
for different T
AMB, MAX
for frame
sizes E and F at 500 V, using SFAVM in High torque mode
(160% over torque).
Figure 4.32: Derating of I
out
for different T
AMB, MAX
for frame
sizes E and F at 500 V, using 60
º
AVM in Normal torque
mode (110% over torque)
Figure 4.33: Derating of I
out
for different T
AMB, MAX
for frame
sizes E and F at 500 V, using SFAVM in Normal torque mode
(110% over torque)
60
º
AVM - Pulse Width Modulation, 525–690 V
Figure 4.34: Derating of I
out
for different T
AMB, MAX
for frame
sizes E and F at 690 V, using 60
º
AVM in High torque mode
(160% over torque).
SFAVM - Stator Frequency Asyncron Vector Modulation, 525–
690 V
Figure 4.35: Derating of I
out
for different T
AMB, MAX
for frame
sizes E and F at 690 V, using SFAVM in High torque mode
(160% over torque).
4 AutomationDrive FC 300 Selection
FC 300 Design Guide
4-36
MG.33.BC.22 - VLT
®
is a registered Danfoss trademark