![Danfoss FC 300 Design Manual Download Page 65](http://html.mh-extra.com/html/danfoss/fc-300/fc-300_design-manual_507599065.webp)
Line Power Supply 3 x 380–500 V AC (AutomationDrive FC 302), 3 x 380–480 V AC (AutomationDrive FC 301)
AutomationDrive FC
301/AutomationDrive
FC 302
P30K
P37K
P45K
P55K
P75K
High/ Normal Load*
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft output
[kW]
30
37
37
45
45
55
55
75
75
90
Enclosure IP20
B4
C3
C3
C4
C4
Enclosure
IP21
C1
C1
C1
C2
C2
Enclosure IP55, 66
C1
C1
C1
C2
C2
Output current
Continuous
(3 x 380-440 V) [A]
61
73
73
90
90
106
106
147
147
177
Intermittent (60 sec
overload)
(3 x 380–440 V) [A]
91.5
80.3
110
99
135
117
159
162
221
195
Continuous
(3 x 441–500 V) [A]
52
65
65
80
80
105
105
130
130
160
Intermittent (60 sec
overload)
(3 x 441–500 V) [A]
78
71.5
97.5
88
120
116
158
143
195
176
Continuous kVA
(400 V AC) [kVA]
42.3
50.6
50.6
62.4
62.4
73.4
73.4
102
102
123
Continuous kVA
(460 V AC) [kVA]
51.8
63.7
83.7
104
128
Max. input current
Continuous
(3 x 380–440 V) [A]
55
66
66
82
82
96
96
133
133
161
Intermittent (60 sec
overload)
(3 x 380–440 V) [A]
82.5
72.6
99
90.2
123
106
144
146
200
177
Continuous
(3 x 441–500 V) [A]
47
59
59
73
73
95
95
118
118
145
Intermittent (60 sec
overload)
(3 x 441–500 V) [A]
70.5
64.9
88.5
80.3
110
105
143
130
177
160
Max. cable size IP20,
line power and motor
[mm
2
(AWG
2)
)]
35 (2)
50 (1)
50 (1)
95 (4/0)
150 (300 mcm)
Max. cable size IP20,
load share and brake
[mm
2
(AWG
2)
)]
35 (2)
50 (1)
50 (1)
95 (4/0)
95 (4/0)
Max. cable size,
IP21/55/66 [mm
2
(AWG
2)
)]
90 (3/0)
90 (3/0)
90 (3/0)
120 (4/0)
120 (4/0)
Max cable size with line
power disconnect
35 (2)
70 (3/0)
150 (300 mcm)
Max. electrical fuses
[A]
1
100
125
160
250
250
Estimated power loss
at rated max. load [W]
4)
570
698
697
843
891
1083
1022
1384
1232
1474
Weight,
enclosure IP21, IP 55,
66 [kg]
45
45
45
65
65
Efficiency
4)
0.98
0.98
0.98
0.98
0.99
* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s
FC 300 Design Guide
4 AutomationDrive FC 300 Selection
MG.33.BC.22 - VLT
®
is a registered Danfoss trademark
4-5
4