![Danfoss FC 300 Design Manual Download Page 87](http://html.mh-extra.com/html/danfoss/fc-300/fc-300_design-manual_507599087.webp)
AutomationDrive FC 300, P7K5T2
Cable
length [m]
AC line
voltage [V]
Rise time [
μ
sec]
Upeak
[kV]
du/dt [kV/
μ
sec]
36
240
0.264
0.624
1.890
136
240
0.536
0.596
0.889
150
240
0.568
0.568
0.800
AutomationDrive FC 300, P11KT2
Cable
length [m]
AC line
voltage [V]
Rise time
[
μ
sec]
Upeak
[kV]
du/dt
[kV/
μ
sec]
30
240
0.556
0.650
0.935
100
240
0.592
0.594
0.802
150
240
0.708
0.587
0.663
AutomationDrive FC 300, P15KT2
Cable
length [m]
AC line
voltage [V]
Rise time
[
μ
sec]
Upeak
[kV]
du/dt
[kV/
μ
sec]
36
240
0.244
0.608
1.993
136
240
0.568
0.580
0.816
150
240
0.720
0.574
0.637
AutomationDrive FC 300, P18KT2
Cable
length [m]
AC line
voltage [V]
Rise time
[
μ
sec]
Upeak
[kV]
du/dt
[kV/
μ
sec]
36
240
0.244
0.608
1.993
136
240
0.568
0.580
0.816
150
240
0.720
0.574
0.637
AutomationDrive FC 300, P22KT2
Cable
length [m]
AC line
voltage [V]
Rise time
[
μ
sec]
Upeak
[kV]
du/dt
[kV/
μ
sec]
15
240
0.194
0.626
2.581
50
240
0.252
0.574
1.822
150
240
0.488
0.538
0.882
AutomationDrive FC 300, P30KT2
Cable
length [m]
AC line
voltage [V]
Rise time
[
μ
sec]
Upeak
[kV]
du/dt
[kV/
μ
sec]
30
240
0.300
0.598
1.594
100
240
0.536
0.566
0.844
150
240
0.776
0.546
0.562
AutomationDrive FC 300, P37KT2
Cable
length [m]
AC line
voltage [V]
Rise time
[
μ
sec]
Upeak
[kV]
du/dt
[kV/
μ
sec]
30
240
0.300
0.598
1.594
100
240
0.536
0.566
0.844
150
240
0.776
0.546
0.562
FC 300 Design Guide
4 AutomationDrive FC 300 Selection
MG.33.BC.22 - VLT
®
is a registered Danfoss trademark
4-27
4