Line Power Supply 3 x 525–690 V AC
AutomationDrive FC
302
P37K
P45K
P55K
P75K
P90K
High/ Normal Load*
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft output at
550 V [kW]
30
37
37
45
45
55
55
75
75
90
Typical Shaft output at
575 V [HP]
40
50
50
60
60
75
75
100
100
125
Typical Shaft output at
690 V [kW]
37
45
45
55
55
75
75
90
90
110
Enclosure
IP21
D1
D1
D1
D1
D1
Enclosure IP54
D1
D1
D1
D1
D1
Enclosure
IP00
D3
D3
D3
D3
D3
Output current
Continuous
(at 550 V) [A]
48
56
56
76
76
90
90
113
113
137
Intermittent (60 sec
overload)
(at 550 V) [A]
77
62
90
84
122
99
135
124
170
151
Continuous
(at 575/690 V) [A]
46
54
54
73
73
86
86
108
108
131
Intermittent (60 sec
overload)
(at 575/690 V) [A]
74
59
86
80
117
95
129
119
162
144
Continuous KVA
(at 550 V) [KVA]
46
53
53
72
72
86
86
108
108
131
Continuous KVA
(at 575 V) [KVA]
46
54
54
73
73
86
86
108
108
130
Continuous KVA
(at 690 V) [KVA]
55
65
65
87
87
103
103
129
129
157
Max. input current
Continuous
(at 550 V) [A]
53
60
60
77
77
89
89
110
110
130
Continuous
(at 575 V) [A]
51
58
58
74
74
85
85
106
106
124
Continuous
(at 690 V) [A]
50
58
58
77
77
87
87
109
109
128
Max. cable size, line
power, motor, load
share and brake [mm
2
(AWG)]
2x70 (2x2/0)
Max. external electrical
fuses [A]
1
125
160
200
200
250
Estimated power loss
at 600 V [W]
4)
1299
1398
1459
1645
1643
1827
1827
2156
2158
2532
Estimated power loss
at 690 V [W]
4)
1355
1458
1459
1717
1721
1913
1913
2262
2264
2662
Weight,
enclosure IP21, IP 54
[kg]
96
Weight,
enclosure IP00 [kg]
82
Efficiency
4)
0.97
0.97
0.98
0.98
0.98
Output frequency
0–600 Hz
Heatsink overtemp.
trip
185°F [85°C]
Power card ambient
trip
140°F [60°C]
* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s
4 AutomationDrive FC 300 Selection
FC 300 Design Guide
4-14
MG.33.BC.22 - VLT
®
is a registered Danfoss trademark