![Danfoss FC 300 Design Manual Download Page 71](http://html.mh-extra.com/html/danfoss/fc-300/fc-300_design-manual_507599071.webp)
Line Power Supply 3 x 525–600 VAC
AutomationDrive FC 302
P37K
P45K
P55K
P75K
High/ Normal
Load*
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft Output [kW]
37
45
45
55
55
75
75
90
Enclosure IP21, 55, 66
C1
C1
C1
C2
C2
Enclosure IP20
C3
C3
C3
C4
C4
Output current
Continuous
(3 x 525–550 V) [A]
54
65
65
87
87
105
105
137
Intermittent
(3 x 525–550 V) [A]
81
72
98
96
131
116
158
151
Continuous
(3 x 525–600 V) [A]
52
62
62
83
83
100
100
131
Intermittent
(3 x 525–600 V) [A]
78
68
93
91
125
110
150
144
Continuous kVA (550 V AC)
[kVA]
51.4
61.9
61.9
82.9
82.9
100.0
100.0
130.5
Continuous kVA (575 V AC)
[kVA]
51.8
61.7
61.7
82.7
82.7
99.6
99.6
130.5
Max. cable size IP20
(line power, motor)
[AWG]
2)
[mm
2
]
50 (1)
95 (4/0)
150 (300 mcm)
Max. cable size IP20
(load share, brake)
[AWG]
2)
[mm
2
]
50 (1)
95 (4/0)
Max. cable size IP21, 55, 66
(line power, motor, load share
and brake)
[AWG]
2)
[mm
2
]
90 (3/0)
120 (4/0)
Max cable size with line power
disconnect
35 (2)
70 (3/0)
150 (300 mcm)
Max. input current
Continuous
at 550 V [A]
49
59
59
78.9
78.9
95.3
95.3
124.3
Intermittent
at 550 V [A]
74
65
89
87
118
105
143
137
Continuous
at 575 V [A]
47
56
56
75
75
91
91
119
Intermittent
at 575 V [A]
70
62
85
83
113
100
137
131
Max. electrical fuses
1)
[A]
125
160
250
250
Environment
Estimated power loss
at rated max. load [W]
4)
850
1100
1400
1500
Weight,
enclosure IP20 [kg]
35
35
50
50
Weight,
enclosure IP21, 55 [kg]
45
45
65
65
Efficiency
4)
0.98
0.98
0.98
0.98
FC 300 Design Guide
4 AutomationDrive FC 300 Selection
MG.33.BC.22 - VLT
®
is a registered Danfoss trademark
4-11