![Danfoss FC 300 Design Manual Download Page 183](http://html.mh-extra.com/html/danfoss/fc-300/fc-300_design-manual_507599183.webp)
525–690 V*, frame sizes B and C
kW
Max. prefuse
Bussmann
E52273
RK1/JDDZ
Bussmann
E4273
J/JDDZ
Bussmann
E4273
T/JDDZ
SIBA
E180276
RK1/JDDZ
LittelFuse
E81895
RK1/JDDZ
Ferraz-
Shawmut
E163267/
E2137
RK1/JDDZ
Ferraz-
Shawmut
E2137
J/HSJ
11K
30 A
KTS-R-30
JKS-30
JKJS-30
5017906-030
KLSR030
A6K-30R
HST30
15K-18K5
45 A
KTS-R-45
JKS-45
JJS-45
5014006-050
KLSR045
A6K-45R
HST45
22K
60 A
KTS-R-60
JKS-60
JJS-60
5014006-063
KLSR060
A6K-60R
HST60
30K
80 A
KTS-R-80
JKS-80
JJS-80
5014006-080
KLSR075
A6K-80R
HST80
37K
90 A
KTS-R-90
JKS-90
JJS-90
5014006-100
KLSR090
A6K-90R
HST90
45K
100 A
KTS-R-100
JKS-100
JJS-100
5014006-100
KLSR100
A6K-100R
HST100
55K
125 A
KTS-R-125
JKS-125
JJS-125
2028220-125
KLS-125
A6K-125R
HST125
75K
150 A
KTS-R-150
JKS-150
JJS-150
2028220-150
KLS-150
A6K-150R
HST150
* UL compliance only 525–600 V
380–500 V, frame sizes D, E and F
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240 V, or 480 V, or 500 V, or 600 V depending on
the drive voltage rating. With the proper fusing, the drive Short Circuit Current Rating (SCCR) is 100,000 Arms.
Size/
Type
Bussmann
E1958
JFHR2**
Bussmann
E4273
T/JDDZ**
SIBA
E180276
JFHR2
LittelFuse
E71611
JFHR2**
Ferraz-
Shawmut
E76491
JFHR2
Bussmann
E4274
H/JDDZ**
Bussmann
E125085
JFHR2*
Internal
Option
Bussmann
P90K
FWH-
300
JJS-
300
2061032.
315
L50S-300
6.6URD30D08A
0315
NOS-
300
170M3017
170M3018
P110
FWH-
350
JJS-
350
2061032.
35
L50S-350
6.6URD30D08A
0350
NOS-
350
170M3018
170M3018
P132
FWH-
400
JJS-
400
2061032.
4
L50S-400
6.6URD30D08A
0400
NOS-
400
170M4012
170M4016
P160
FWH-
500
JJS-
500
2061032.
5
L50S-500
6.6URD30D08A
0500
NOS-
500
170M4014
170M4016
P200
FWH-
600
JJS-
600
2062032.
63
L50S-600
6.6URD32D08A
630
NOS-
600
170M4016
170M4016
Table 8.2: Frame size D, Line fuses, 380–500 V
Size/Type
Bussmann PN*
Rating
Ferraz
Siba
P250
170M4017
700 A, 700 V
6.9URD31D08A0700
20 610 32.700
P315
170M6013
900 A, 700 V
6.9URD33D08A0900
20 630 32.900
P355
170M6013
900 A, 700 V
6.9URD33D08A0900
20 630 32.900
P400
170M6013
900 A, 700 V
6.9URD33D08A0900
20 630 32.900
Table 8.3: Frame size E, Line fuses, 380–500 V
Size/Type
Bussmann PN*
Rating
Siba
Internal Bussmann Option
P450
170M7081
1600 A, 700 V
20 695 32.1600
170M7082
P500
170M7081
1600 A, 700 V
20 695 32.1600
170M7082
P560
170M7082
2000 A, 700 V
20 695 32.2000
170M7082
P630
170M7082
2000 A, 700 V
20 695 32.2000
170M7082
P710
170M7083
2500 A, 700 V
20 695 32.2500
170M7083
P800
170M7083
2500 A, 700 V
20 695 32.2500
170M7083
Table 8.4: Frame size F, Line fuses, 380–500 V
Size/Type
Bussmann PN*
Rating
Siba
P450
170M8611
1100 A, 1000 V
20 781 32.1000
P500
170M8611
1100 A, 1000 V
20 781 32.1000
P560
170M6467
1400 A, 700 V
20 681 32.1400
P630
170M6467
1400 A, 700 V
20 681 32.1400
P710
170M8611
1100 A, 1000 V
20 781 32.1000
P800
170M6467
1400 A, 700 V
20 681 32.1400
Table 8.5: Frame size F, Inverter module DC Link Fuses, 380–500 V
*170M fuses from Bussmann shown use the -/80 visual indicator; -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage
may be substituted for external use
**Any minimum 500 V UL listed fuse with associated current rating may be used to meet UL requirements.
FC 300 Design Guide
8 Electrical Installation
MG.33.BC.22 - VLT
®
is a registered Danfoss trademark
8-25
8