AutomationDrive FC 302 - Line power: 200–240V (T2) - 10% Duty Cycle
AutomationDrive FC
302
P
m (HO)
R
min
R
br, nom
R
rec
P
br avg
Order no.
Period
Cable cross-
section
2
*
Therm. relay
Max. brake tor-
que with Rrec*
T2
[kW]
[
Ω
]
[
Ω
]
[
Ω
]
[kW]
175Uxxxx
[s]
[mm2]
[A]
[%]
PK25
0.25
382
467
425
0.095
1841
120
1.5
0.5
160 (160)
PK37
0.37
279
315
310
0.25
1842
120
1.5
0.9
160 (160)
PK55
0.55
189
211
210
0.285
1843
120
1.5
1.2
160 (160)
PK75
0.75
130
154
145
0.065
1820
120
1.5
0.7
160 (160)
P1K1
1.1
81
104
90
0.095
1821
120
1.5
1
160 (160)
P1K5
1.5
58.5
75.7
65
0.25
1822
120
1.5
2
160 (160)
P2K2
2.2
45
51
50
0.285
1823
120
1.5
2.4
160 (160)
P3K0
3
31.5
37
35
0.43
1824
120
1.5
2.5
160 (160)
P3K7
3.7
22.5
29.6
25
0.8
1825
120
1.5
5.7
160 (160)
AutomationDrive FC 301/302 - Line power: 200–240 V (T2) - 10% Duty Cycle
AutomationDrive
FC 301/302
P
m (HO)
R
min
R
br. nom
R
rec
P
br avg
Order no.
Period
Cable cross-
section
2
*
Therm.
relay
Max. brake tor-
que with R
rec
*
T2
[kW]
[
Ω
]
[
Ω
]
[
Ω
]
[kW]
175Uxxxx
[s]
[mm2]
[A]
[%]
P5K5
5.5
18
20
20
1
1826
120
1.5
7.1
158 (160)
P7K5
7.5
13
14
15
2
1827
120
1.5
11
153 (160)
P11K
11
9
10
10
2.8
1828
120
2.5
17
154 (160)
P15K
15
6
7
7
4
1829
120
4
24
150 (150)
P18K
18.5
5.1
6
6
4.8
1830
120
4
28
150 (150)
P22K
22
4.2
5
4.7
6
1954
300
10
36
150 (150)
P30K
30
3
3.7
3.3
8
1955
300
10
49
150 (150)
P37K
37
2.4
3
2.7
10
1956
300
16
61
150 (150)
FC 300 Design Guide
5 How to Order
MG.33.BC.22 - VLT
®
is a registered Danfoss trademark
5-9