![Danfoss FC 300 Design Manual Download Page 193](http://html.mh-extra.com/html/danfoss/fc-300/fc-300_design-manual_507599193.webp)
Installation of 24 Volt external DC Supply
Torque: 0.5–0.6 Nm (5 in-lbs)
Screw size: M3
No.
Function
35 (-), 36 (+)
24 V external DC supply
24 VDC external supply can be used as low-voltage supply to the control card and any option cards installed. This enables full operation of the LCP
(including parameter setting) without connection to line power. Please note that a warning of low voltage will be given when 24 V DC has been connected;
however, there will be no tripping.
Use 24 V DC supply of type PELV to ensure correct galvanic isolation (type PELV) on the control terminals of the adjustable frequency
drive.
FC 300 Design Guide
8 Electrical Installation
MG.33.BC.22 - VLT
®
is a registered Danfoss trademark
8-35
8