Frame Size
Power Size
Voltage [V]
1 cable [m]
2 cables [m]
3 cables [m]
4 cables [m]
A1, A2, A5
0.5-1 hp [0.37–0.75
kW]
400
150
45
8
6
500
150
7
4
3
A2, A5
1.5–2 hp [1.1–1.5
kW]
400
150
45
20
8
500
150
45
5
4
A2, A5
3–5 hp [2.2–4 kW]
400
150
45
20
11
500
150
45
20
6
A3, A5
7.5–10 hp [5.5–7.5
kW]
400
150
45
20
11
500
150
45
20
11
B1, B2, B3, B4,
C1, C2, C3, C4
11-75 kW
400
150
75
50
37
500
150
75
50
37
Problems may arise at start and at low RPM values if motor sizes are widely different because small motors' relatively high ohmic resistance in the stator
calls for a higher voltage at start and at low RPM values.
The electronic thermal relay (ETR) of the adjustable frequency drive cannot be used as motor protection for the individual motor of systems with parallel-
connected motors. Provide further motor protection with, for example, thermistors in each motor or individual thermal relays (circuit breakers are not a
suitable means of protection).
FC 300 Design Guide
8 Electrical Installation
MG.33.BC.22 - VLT
®