10 Options and Accessories
Danfoss offers a wide range of options and accessories for VLT AutomationDrive.
10.1.1 Mounting of Option Modules in Slot A
Slot A position is dedicated to serial communication bus options. For further information, see the Instruction Manual.
10.1.2 Mounting Option Modules in Slot B
The power to the adjustable frequency drive must be disconnected.
It is strongly recommended to make sure the parameter data is saved (e.g., by MCT10 software) before option modules are inserted/removed from the
drive.
•
Remove the LCP (Local Control Panel), the terminal cover, and the LCP frame from the adjustable frequency drive.
•
Insert the MCB10x option card into slot B.
•
Connect the control cables and relieve the cable by the enclosed cable strips.
* Remove the knock-out in the extended LCP frame, so that the option will fit under the extended LCP frame.
•
Fit the extended LCP frame and terminal cover.
•
Fit the LCP or blind cover in the extended LCP frame.
•
Connect power to the adjustable frequency drive.
•
Set up the input/output functions in the corresponding parameters, as mentioned in the section
General Technical Data
.
Frame sizes A2, A3 and B3
Frame sizes A5, B1, B2, B4, C1, C2, C3 and C4
FC 300 Design Guide
10 Options and Accessories
MG.33.BC.22 - VLT
®
is a registered Danfoss trademark
10-1
10