AutomationDrive FC 301 - Line power: 380–480 V (T4) - 10% Duty Cycle
AutomationDrive FC
301
P
m (HO)
R
min
R
br. nom
R
rec
P
br avg
Order no.
Period
Cable cross-
section
2
*
Therm. re-
lay
Max. brake tor-
que with R
rec
*
T4
[kW]
[
Ω
]
[
Ω
]
[
Ω
]
[kW]
175Uxxxx
[s]
[mm2]
[A]
[%]
PK37
0.37
620
1098
620
0.065
1840
120
1.5
0.3
160 (160)
PK55
0.55
620
739
620
0.065
1840
120
1.5
0.3
160 (160)
PK75
0.75
485
539
620
0.065
1840
120
1.5
0.3
139 (160)
P1K1
1.1
329
366
425
0.095
1841
120
1.5
0.5
138 (160)
P1K5
1.5
240
266
310
0.25
1842
120
1.5
0.9
138 (160)
P2K2
2.2
161
179
210
0.285
1843
120
1.5
1.2
137 (160)
P3K0
3
117
130
150
0.43
1844
120
1.5
1.7
139 (160)
P4K0
4
87
97
110
0.6
1845
120
1.5
2.3
140 (160)
P5K5
5.5
63
69
80
0.85
1846
120
1.5
3.3
139 (160)
P7K5
7.5
45
50
65
1
1847
120
1.5
3.9
124 (160)
P11K
11
34.9
38.8
40
1.8
1848
120
1.5
7.1
155 (160)
P15K
15
25.3
28.1
30
2.8
1849
120
1.5
9.7
150 (160)
P18K
18.5
20.3
22.6
25
3.5
1850
120
1.5
12
144 (160)
P22K
22
16.9
18.8
20
4
1851
120
1.5
14
150 (160)
P30K
30
13.2
14.7
15
4.8
1852
120
2.5
18
147 (150)
P37K
37
11
12
12
5.5
1853
120
2.5
21
147 (150)
P45K
45
9
10
9.8
15
2008
120
10
39
148 (150)
P55K
55
7
8
7.3
13
0069
120
10
42
150 (150)
P55K
55
6.6
7.9
5.7
14
1958
300
10
50
150 (150)
P75K
75
6.6
5.7
6.3
15
0067
120
10
49
150 (150)
P75K
75
4.2
5.7
4.7
18
1959
300
16
62
150 (150)
P75K
75
4.2
5.7
4.7
29
0077
600
16
79
150 (150)