![Danfoss FC 300 Design Manual Download Page 64](http://html.mh-extra.com/html/danfoss/fc-300/fc-300_design-manual_507599064.webp)
Line Power Supply 3 x 380–500 V AC (AutomationDrive FC 302), 3 x 380–480 V AC (AutomationDrive FC 301)
AutomationDrive FC 301/
AutomationDrive FC 302
P11K
P15K
P18K
P22K
High/ Normal Load*
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft output [kW]
11
15
15
18.5
18.5
22.0
22.0
30.0
Enclosure IP20
B3
B3
B4
B4
Enclosure
IP21
B1
B1
B2
B2
Enclosure IP55, 66
B1
B1
B2
B2
Output current
Continuous
(3 x 380-440 V) [A]
24
32
32
37.5
37.5
44
44
61
Intermittent (60 sec over-
load)
(3 x 380–440 V) [A]
38.4
35.2
51.2
41.3
60
48.4
70.4
67.1
Continuous
(3 x 441–500 V) [A]
21
27
27
34
34
40
40
52
Intermittent (60 sec over-
load)
(3 x 441–500 V) [A]
33.6
29.7
43.2
37.4
54.4
44
64
57.2
Continuous kVA
(400 V AC) [kVA]
16.6
22.2
22.2
26
26
30.5
30.5
42.3
Continuous kVA
(460 V AC) [kVA]
21.5
27.1
31.9
41.4
Max. input current
Continuous
(3 x 380–440 V) [A]
22
29
29
34
34
40
40
55
Intermittent (60 sec over-
load)
(3 x 380–440 V) [A]
35.2
31.9
46.4
37.4
54.4
44
64
60.5
Continuous
(3 x 441–500 V) [A]
19
25
25
31
31
36
36
47
Intermittent (60 sec over-
load)
(3 x 441–500 V) [A]
30.4
27.5
40
34.1
49.6
39.6
57.6
51.7
Max. cable size [mm
2
/
AWG]
2)
16/6
16/6
35/2
35/2
Max cable size with line
power disconnect
16/6
Max. electrical fuses [A]
1
63
63
63
80
Estimated power loss
at rated max. load [W]
4)
291
392
379
465
444
525
547
739
Weight, enclosure IP20
12
12
23.5
23.5
Weight,
enclosure IP21, IP 55, 66
[kg]
23
23
27
27
Efficiency
4)
0.98
0.98
0.98
0.98
* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s
4 AutomationDrive FC 300 Selection
FC 300 Design Guide
4-4
MG.33.BC.22 - VLT
®
is a registered Danfoss trademark
4