Service Settings
EY.65.H4.02
69
Figure 9. The heat circuit and the hot-water circuit can be operated at the same time
Total stop
These parameters determine how the individual heat circuits are operated during night
setback:
Display text
Parameter
Default value,
range
Description
Heat circuit 1,
Heat circuit 2
Default value:
OFF
Range:
ON, OFF
When Total stop for a heat circuit is set
to ON, the circulation pump is switched
off and the motor valve is closed com-
pletely
When Total stop is set to OFF, the heat
circuits are controlled according to the
night setback temperature setting
Safety thermostat
The safety thermostat function allows you to specify a maximum limit for the flow
temperature of all circuit types.
Display text
Parameter
Default value,
range
Description
Heat circuit 1
Heat circuit 2
Hot water
Default value:
150 °C
Range:
0-200 °C
The maximum flow temperature for the
individual circuits. If the flow tempera-
ture rises 5 K above this setting, the
motor valve supplying the circuit is
driven towards the closed position
When the flow temperature has fallen to
5 K below the specified temperature,
normal control takes over again
Summary of Contents for ECL 2000
Page 1: ...User s Guide ECL 2000 11 99 EY 65 H4 02...
Page 2: ......
Page 3: ...User s Guide ECL 2000 Danfoss A S EY 65 H4 02...
Page 8: ...Introduction EY 65 H4 02 2 This page is intentionally left blank...
Page 30: ...Weather Compensation Curves EY 65 H4 02 24 This page is intentionally left blank...
Page 67: ...Service Settings EY 65 H4 02 61 This page is intentionally left blank...
Page 92: ...Appendix B Service Menus EY 65 H4 02 86...
Page 98: ...Glossary EY 65 H4 02 92 This page is intentionally left blank...
Page 100: ...References EY 65 H4 02 94 This page is intentionally left blank...
Page 106: ...Index EY 65 H4 02 100...