Service Settings
EY.65.H4.02
52
10.3.1 Hot Water Settings
This section describes the options you can set in menus under the Hot Water menu
item.
Anti-bacteria function
When this function is active, the hot-water temperature is raised once in a 24-hour
period to a user-defined temperature and for a user-defined length of time. The con-
troller accomplishes this by temporarily raising the hot-water temperature setpoint.
The following parameters can be set:
Display text
Parameter
Default value,
range
Description
Duration
Default value:
0.0 hours
Range:
0-23:45 hours
The period during which the water tem-
perature will be maintained at the in-
creased level. If this parameter is set to
0, the anti-bacteria function is disabled
Start time
Default value:
23:00
Range:
0:00-23:45
The time of day at which the temperature
starts to increase
Temperature
Default value:
70 °C
Range:
1-99 °C
The hot-water temperature setpoint will
be increased to this level
Summary of Contents for ECL 2000
Page 1: ...User s Guide ECL 2000 11 99 EY 65 H4 02...
Page 2: ......
Page 3: ...User s Guide ECL 2000 Danfoss A S EY 65 H4 02...
Page 8: ...Introduction EY 65 H4 02 2 This page is intentionally left blank...
Page 30: ...Weather Compensation Curves EY 65 H4 02 24 This page is intentionally left blank...
Page 67: ...Service Settings EY 65 H4 02 61 This page is intentionally left blank...
Page 92: ...Appendix B Service Menus EY 65 H4 02 86...
Page 98: ...Glossary EY 65 H4 02 92 This page is intentionally left blank...
Page 100: ...References EY 65 H4 02 94 This page is intentionally left blank...
Page 106: ...Index EY 65 H4 02 100...