Service Settings
EY.65.H4.02
56
10.3.2 Pump/Valve Settings
This section describes the parameters you can set in pictures under the Pump/valve
menu item.
Pump
This group of settings determines how pumps in the system operate.
Display text
Parameter
Default value,
range
Description
Max. charge
Maximum
charging pe-
riod
Default value:
40 min.
Range:
20-200 min.
No charging is allowed after the elapse
of the maximum charging period
Overrun
Overrun pe-
riod
Default value:
3 min.
Range:
0-9 min.
The maximum time that the pump is al-
lowed to run after charging has ended or
after a change from comfort to night set-
back mode
Prerun
Prerun period
Default value:
3 min.
Range:
0-9 min.
Delay before the charging pump is
started
During charging
This group of settings determines how pumps in the system operate during charging.
Display text
Parameter
Default value,
range
Description
Circulation
Default value:
YES
Range:
YES, NO
When this parameter is set to YES, the
circulation pump is active according to
the 24-hour program for the hot-water
service. If the parameter is set to NO, the
pump is stopped during charging
Pump func-
tion
Default value:
YES
Range:
YES, NO
This setting allows the controller to take
into consideration a slightly different
type of circuit where a changeover valve
is used instead of a pump.
When a pump is used, Pump function
must be set to YES. When a changeover
valve is used, the setting must be NO
Summary of Contents for ECL 2000
Page 1: ...User s Guide ECL 2000 11 99 EY 65 H4 02...
Page 2: ......
Page 3: ...User s Guide ECL 2000 Danfoss A S EY 65 H4 02...
Page 8: ...Introduction EY 65 H4 02 2 This page is intentionally left blank...
Page 30: ...Weather Compensation Curves EY 65 H4 02 24 This page is intentionally left blank...
Page 67: ...Service Settings EY 65 H4 02 61 This page is intentionally left blank...
Page 92: ...Appendix B Service Menus EY 65 H4 02 86...
Page 98: ...Glossary EY 65 H4 02 92 This page is intentionally left blank...
Page 100: ...References EY 65 H4 02 94 This page is intentionally left blank...
Page 106: ...Index EY 65 H4 02 100...