Weather Compensation Curves
EY.65.H4.02
22
7.1 Adjusting the Flow Temperature Curve
The weather compensation curve for the flow temperature can be modified by setting:
A maximum and minimum value, 2 curve endpoints and, in addition to these, 3 break
points. Together, these parameters define the shape of the curve.
,
1.
Press
to select the desired heat circuit.
2.
Press
to display the flow temperature curve.
!
Note:
If you press
while a hot-water circuit is selected, the ECL 2000 displays a pop-up
informing you that this facility is not available for hot-water circuits.
Moving curve
points
3.
Press
to display the currently defined curve
points.
4.
Use
and
to move the cursor to the point you
wish to modify.
The flow temperature (y co-ordinate) of the selected
point is highlighted to indicate that it can be modified.
5.
Use
and
to select either the flow tempera-
ture (y co-ordinate) or the outdoor temperature (x
co-ordinate) of the point.
6.
Use
and
to adjust the selected value.
!
Note:
If two curve points are placed in the same position, one point is automatically re-
moved.
Setting maximum
and minimum val-
ues
7.
Ensure that the outdoor temperature of a point is
selected (x co-ordinate value highlighted), and
press
to display maximum and minimum val-
ues.
8.
Use
and
to select either the maximum or
minimum setting.
9.
Use
and
to adjust the selected setting.
Adding and re-
moving curve
points
10.
Ensure that the curve’s minimum value is selected,
and press
to display break points.
The checked box indicates the number of break points
that are currently active (in this example, 1 break point
is active – in addition to the two curve endpoints).
11. Use
to add a breakpoint or
to remove one.
Summary of Contents for ECL 2000
Page 1: ...User s Guide ECL 2000 11 99 EY 65 H4 02...
Page 2: ......
Page 3: ...User s Guide ECL 2000 Danfoss A S EY 65 H4 02...
Page 8: ...Introduction EY 65 H4 02 2 This page is intentionally left blank...
Page 30: ...Weather Compensation Curves EY 65 H4 02 24 This page is intentionally left blank...
Page 67: ...Service Settings EY 65 H4 02 61 This page is intentionally left blank...
Page 92: ...Appendix B Service Menus EY 65 H4 02 86...
Page 98: ...Glossary EY 65 H4 02 92 This page is intentionally left blank...
Page 100: ...References EY 65 H4 02 94 This page is intentionally left blank...
Page 106: ...Index EY 65 H4 02 100...