Service Settings
EY.65.H4.02
65
10.4.2 Alarm
Status
This group of pictures allow the operator to read the current alarm status. Alarms can
be generated based on measurement data from all relevant sensors, i.e. depending on
the selected application, there are a number of Alarm Status pictures. There is an
Alarm Status picture for every sensor that has an alarm setup, as explained on page
66. Figure 8 explains the different alarm status values and their relation to the alarm
limits that are specified in the Alarm Setup pictures.
Alarm status:
Min range
Low limit
Normal
High limit
Max range
Temperature
Max
High
Min
Low
Limit:
Figure 8. Alarm limits and status intervals
Note:
All the parameters in the Alarm Status pictures are read-only.
Display text
Parameter
Default value,
range
Description
Actual
The actual value of the measured tem-
perature
Date, Time
The date and time of the last change in
alarm status
Status
Range:
Min range,
Low limit,
Normal,
High limit,
Max range,
Disabled,
Fault
The current alarm status
When Status has the value Disabled, all
alarms from the sensor are disabled. No
internal alarms are generated, and if P3 is
set up as an alarm output, the output does
not change
When Status has the value Fault, this
indicates that the sensor is not connected
or there is a sensor error
Previous
Range:
Min range,
Low limit,
Normal,
High limit,
Max range,
Fault
The previous alarm status, i.e. the alarm
status before the latest status change
Summary of Contents for ECL 2000
Page 1: ...User s Guide ECL 2000 11 99 EY 65 H4 02...
Page 2: ......
Page 3: ...User s Guide ECL 2000 Danfoss A S EY 65 H4 02...
Page 8: ...Introduction EY 65 H4 02 2 This page is intentionally left blank...
Page 30: ...Weather Compensation Curves EY 65 H4 02 24 This page is intentionally left blank...
Page 67: ...Service Settings EY 65 H4 02 61 This page is intentionally left blank...
Page 92: ...Appendix B Service Menus EY 65 H4 02 86...
Page 98: ...Glossary EY 65 H4 02 92 This page is intentionally left blank...
Page 100: ...References EY 65 H4 02 94 This page is intentionally left blank...
Page 106: ...Index EY 65 H4 02 100...