Manual Override
EY.65.H4.02
36
9. MANUAL
OVERRIDE
When the ECL 2000’s Manual Override function is active, you can control system
components, circulation pumps and valve motors from the ECL 2000’s front panel.
,
1.
Press
to select the circuit that you wish to con-
trol manually.
2.
Press
to activate manual control.
The LED above the
button lights up and all four
LED’s indicating the controller’s operating mode are
switched off. The controller displays a picture showing
the pumps and valves of the selected circuit, as well as
status information.
!
Note:
While the Manual Override function is active, automatic control of all circuits in the
plant is disabled. Automatic control is disabled, as long as the LED above the
is
lit.
While Manual Override is active, frost-protection of the plant is disabled.
3.
Press
and
to select the pump or valve you wish to operate (see
facing page).
The text below the selected component is highlighted to indicate the selection.
4.
Press
and
to operate the device. These buttons work as indicated in
the table below.
Push-button
Pump
Motor valve
Pump is set to
ON
Motor valve OPENs while button is pressed. After the but-
ton has been kept depressed for about 5 seconds, the valve
will move continuously towards the open position until the
button is pressed again
Pump is set to
OFF
Motor valve CLOSEs while button is pressed. After the
button has been kept depressed for about 5 seconds, the
valve will move continuously towards the closed position
until the button is pressed again
Note:
If a motor valve is moving when
is pressed, it will continue running. You can stop
the valve by pressing
or
.
It is not possible to control a timer circuit manually.
Summary of Contents for ECL 2000
Page 1: ...User s Guide ECL 2000 11 99 EY 65 H4 02...
Page 2: ......
Page 3: ...User s Guide ECL 2000 Danfoss A S EY 65 H4 02...
Page 8: ...Introduction EY 65 H4 02 2 This page is intentionally left blank...
Page 30: ...Weather Compensation Curves EY 65 H4 02 24 This page is intentionally left blank...
Page 67: ...Service Settings EY 65 H4 02 61 This page is intentionally left blank...
Page 92: ...Appendix B Service Menus EY 65 H4 02 86...
Page 98: ...Glossary EY 65 H4 02 92 This page is intentionally left blank...
Page 100: ...References EY 65 H4 02 94 This page is intentionally left blank...
Page 106: ...Index EY 65 H4 02 100...