Configuring the ECL 2000
EY.65.H4.02
30
8.4.2 Sensor
Inputs
This section explains the setup of the ECL 2000’s sensor inputs. See the ECL 2000
Installation Guide (ref. [2]) for further information.
Note:
It is not possible to set up two sensors with the same function (Sensor) in one circuit
(Circuit). For example, you cannot have two room temperature sensors both affecting
circuit 1. The ECL 2000 automatically excludes this and similar illegal settings.
Furthermore, not all combinations of settings (e.g. Sensor and Type) are allowed. The
ECL 2000 keeps track of this and only allows you to select valid settings.
Sensor
This setting tells the ECL 2000 what is measured by means of the sensor connected to
this input. The setting can have the following values:
Value
Description
Room temp.
Room temperature
Sun intens.
Sun intensity
Wind veloc.
Wind velocity
Flow
Water flow
Energy
Energy measurement
Clock func.
An external timer is connected to the input. Overrides the normal pro-
gram set up for the circuit. When the timer input is OFF (0), the circuit
is in Automatic mode. When the timer input is ON (1), the circuit is in
Comfort mode
Other
Universal limiter
None
No function
Circuit
This parameter determines which circuit is affected by the sensor.
Value
Description
None
No circuits affected
Circuit 1
Heat circuit 1
Circuit 2
Heat circuit 2
Hot water
Hot-water circuit
Circuit 1+2
Circuits 1 and 2
All circuits
All heat and hot-water circuits in the system
Summary of Contents for ECL 2000
Page 1: ...User s Guide ECL 2000 11 99 EY 65 H4 02...
Page 2: ......
Page 3: ...User s Guide ECL 2000 Danfoss A S EY 65 H4 02...
Page 8: ...Introduction EY 65 H4 02 2 This page is intentionally left blank...
Page 30: ...Weather Compensation Curves EY 65 H4 02 24 This page is intentionally left blank...
Page 67: ...Service Settings EY 65 H4 02 61 This page is intentionally left blank...
Page 92: ...Appendix B Service Menus EY 65 H4 02 86...
Page 98: ...Glossary EY 65 H4 02 92 This page is intentionally left blank...
Page 100: ...References EY 65 H4 02 94 This page is intentionally left blank...
Page 106: ...Index EY 65 H4 02 100...