Service Settings
EY.65.H4.02
41
10.2 Heat Circuit Functions
This section describes the parameters that can be set up for a heat circuit via the
service menus.
This picture is the service menu for a heat circuit. Heat
circuit functions are divided into 4 groups correspond-
ing to the menu items: Building, Pump/valve, PI con-
stants and Limiter. See the overview diagram on page
38.
Each menu item gives access to a number of setting pictures allowing you to view and
modify various parameters for the heat circuit. The number of pictures and parameters
available depends on the type of controller you are working with and the application
you have selected (see page 26 for information about ECL 2000 applications).
This section describes all parameters that can be set for a heat circuit. Please disregard
the descriptions of any parameters not available in your specific system setup.
Instructions for operating the ECL 2000’s service menus are provided on page 39.
10.2.1 Building Settings
This section describes the parameters you can set in pictures under the Building menu
item.
Summer cut-off
The summer cut-off function makes the controller close down the heat circuit.
Display text
Parameter
Default value,
range
Description
Outdoor temp.
Outdoor tem-
perature
Default value:
18 °C
Range:
10-30 °C
When the outdoor temperature reaches
this value, summer cut-off is activated,
and the heat circuit it closed down
Room temp.
Room tem-
perature
Default value:
24 °C
Range:
10-30 °C
When the room temperature reaches this
level, summer cut-off is activated
Note:
By default, the circulation pump of the heat circuit is switched off when the calcu-
lated flow temperature drops below 20 °C. See page 45.
Summary of Contents for ECL 2000
Page 1: ...User s Guide ECL 2000 11 99 EY 65 H4 02...
Page 2: ......
Page 3: ...User s Guide ECL 2000 Danfoss A S EY 65 H4 02...
Page 8: ...Introduction EY 65 H4 02 2 This page is intentionally left blank...
Page 30: ...Weather Compensation Curves EY 65 H4 02 24 This page is intentionally left blank...
Page 67: ...Service Settings EY 65 H4 02 61 This page is intentionally left blank...
Page 92: ...Appendix B Service Menus EY 65 H4 02 86...
Page 98: ...Glossary EY 65 H4 02 92 This page is intentionally left blank...
Page 100: ...References EY 65 H4 02 94 This page is intentionally left blank...
Page 106: ...Index EY 65 H4 02 100...