The compressor must only be used for its
designed purpose(s) and within its scope of
application (refer to «operating limits»).
Consult Application guidelines and datasheet
available from cc.danfoss.com
Under all circumstances,
the EN378 (or other
applicable local safety
regulation) requirements
must be fulfilled.
The compressor is delivered under
nitrogen gas pressure (between 0.3 and
0.7 bar) and hence cannot be connected
as is; refer to the «assembly»
section for
further details.
The compressor must be
handled with caution in the
vertical position (maximum
offset from the vertical : 15°)
Installation and servicing of the compressor by qualified personnel only. Follow these instructions and sound refrigeration engineering
practice relating to installation, commissioning, maintenance and service.
A
: Model number
B
: Serial number
C
: Refrigerant
D
: Supply voltage, Starting current & Maximum
operating current
E
: Housing service pressure
F
: Factory charged lubricant
1 – Introduction
These instructions pertain to the Danfoss scroll compressors DSH, SM, SY, SZ, SH, DSF & WSH scroll
compressors used for air-conditioning systems. They provide necessary information regarding safety
and proper usage of this product.
70
65
60
55
50
45
40
Tc (°C
)
To (°C)
SH=5K
SH=30K
35
30
25
20
15
10
5
-35 -30 -25 -20 -15 -10 -5
0
5
10
15
20
25
30
R410A - DSH090-184
70
65
60
55
50
45
40
Tc (°C
)
To (°C)
SH=5K
SH=30K
35
30
25
20
15
10
5
-35 -30 -25 -20 -15 -10 -5
0
5
10
15
20
25
30
70
65
60
55
50
45
40
Tc (°C
)
To (°C)
SH=5K
DSH120/140/161/184
DSH090/105
35
30
25
20
15
10
5
-35 -30 -25 -20 -15 -10 -5
0
5
10
15
20
25
30
R410A - DSH240-600
R452B / R454B - DSH240-485
(dedicated references)
T
C
(°C)
T
0
(°C)
R134a - SY240-380
T
C
(°C)
T
0
(°C)
5
R22 & R417A - SM - SY
T
C
(°C)
T
0
(°C)
R407C Dew point Conditions - SY240-380
T
C
(°C
)
T
0
(°C)
-30
20
25
30
35
40
45
50
55
60
65
70
-25
-20
-15
-10
-5
0
5
10
15
20
R410A - WSH
R410A - SH
5
30
T
C
(°C)
T
0
(°C)
R404A & R507A - SZ084-185
T
C
(°C)
T
0
(°C)
R407C Dew point Conditions - SZ084-185
T
C
(°C)
T
0
(°C)
R134a - SZ084-185
T
C
(°C)
T
0
(°C)
When SM compressors are used with R417A,
the factory charged mineral oil 160P must be
replaced by polyolester oil 160SZ.
3 - Operating map
2- Nameplate
Danfoss scroll compressors
DSH / SM / SY / SZ / SH / WSH
A
D
E
F
B
C
R452B / R454B DSH090-184
(dedicated references)
70
65
60
55
50
45
40
Tc (°C
)
To (°C)
SH=5K
35
30
25
20
15
10
5
-35 -30 -25 -20 -15 -10 -5
0
5
10
15
20
25
30