background image

Instructions

8510197P05F - AN24598649703302en-000501 | 5

© Danfoss | DCS (CC) | 2019.01

5 – Handling and storage

 •  Handle the compressor with care. Use the 

dedicated handles in the packaging. Use the 

compressor lifting lug and use appropriate 

and safe lifting equipment.

 •  Store and transport the compressor in an 

upright position.

 •   Store the compressor between Ts min and Ts 

max values for LP side indicated on compres-

sor nameplate. 

 •   Don’t expose the compressor and the packa-

ging to rain or corrosive atmosphere.

6 – Safety measures before assembly

 Never use the compressor in a flammable at-

mosphere.

 •  Check before assembly that the compressor 

does not show any obvious signs of deteriora-

tion that could have occurred during inappro-

priate transportation, handling or storage.

 •  The compressor ambient temperature may 

not exceed Ts max value for LP side indicated 

on compressor nameplate during off-cycle.

 •  Mount the compressor on a horizontal flat 

surface with less than 3° slope.

 •   Verify that the power supply corresponds to 

the compressor motor characteristics (see 

 

nameplate).

 •  When installing DSH, SH, WSH or SZ, use 

equipment specifically reserved for HFC re-

frigerants which was never used for CFC or 

HCFC refrigerants.

 •   Use clean and dehydrated refrigeration-grade 

copper tubes and silver alloy brazing material.

  •   Use clean and dehydrated system components.

  •   The piping connected to the compressor must be 

flexible in 3 dimensions to dampen vibrations.

7 – Assembly

 •   The compressor must be mounted on rails or 

chassis according to Danfoss recommenda-

tions described in related product guidelines 

(type of spacer, tightening torques).

 •  Slowly release the nitrogen holding charge 

through the schrader port.

 •  Remove the gaskets when brazing rotolock 

connectors.

  •   Always use new gaskets for assembly.

 •  Connect the compressor to the system as 

soon as possible to avoid oil contamination 

from ambient moisture.

  •   Avoid material entering into the system while 

cutting tubes. Never drill holes where burrs 

cannot be removed.

 •  Braze with great care using state-of-the-art 

technique and vent piping with nitrogen gas 

flow.

 •  Connect the required safety and control de-

vices. When the schrader port is used for this, 

remove the internal valve.

 •  

Do not exceed the maximum tightening 

torque for rotolock connections: 

Rotolock connections Tightening torque

1" rotolock

80 Nm

1 1/4 " rotolock

90 Nm

1 3/4" rotolock

110 Nm

2 1/4" rotolock

145 Nm.

8 – Leak detection

 Never pressurize the circuit with oxygen or 

dry air. This could cause fire or explosion.

 •   SM 084 to 185, SY 380, SZ 084 to 185, SZ 380, 

DSH / SH / WSH 090 to 184: Pressurize the 

system on HP side first and then on LP side. 

Never let the pressure on LP side exceed the 

pressure on HP side with more than 5 bar. 

Such pressure difference could cause internal 

compressor damage.

  •   Do not use dye for leak detection.

  •   Perform a leak detection test on the complete 

system.

 •  The test pressure must not exceed 1.1 x PS 

value for LP side and PS value for HP side indi-

cated on compressor nameplate.

  •   When a leak is discovered, repair the leak and 

repeat the leak detection.

9 – Vacuum dehydration

 •  Never use the compressor to evacuate the 

system.

  •   Connect a vacuum pump to both the LP & HP 

sides.

 •   Pull down the system under a vacuum of 500 

µm Hg (0.67 mbar) absolute.

  •   Do not use a megohmmeter nor apply power 

to the compressor while it is under vacuum as 

this may cause internal damage.

10 – Electrical connections

  •   Switch off and isolate the main power supply. 

See overleaf for wiring details.

  •   All electrical components must be selected as 

per local standards and compressor require-

ments.

 •  Refer to section 4 for electrical connections 

details.

 •  The Danfoss scroll compressors only works 

correctly in one rotation direction. Line 

phases L1, L2, L3 must absolutely be connec-

ted to compressor terminals T1, T2, T3 to 

avoid reverse rotation.

 •   Use ø 4.8 mm (3/16”) screws and ¼” ring ter-

minals for the power connection. Fasten with 

3 Nm torque.

  •   The thermostat connection (if present) is a ¼” 

AMP-AWE spade connector.

 •   The compressor must be connected to earth 

with the 5 mm earth terminal screw.

11 – Filling the system

  •   Keep the compressor switched off.

 •  Fill the refrigerant in liquid phase into the 

condenser or liquid receiver. The charge must 

be as close as possible to the nominal system 

charge to avoid low pressure operation and 

excessive superheat. Never let the pressure on 

LP side exceed the pressure on HP side with 

more than 5 bar. Such pressure difference 

could cause internal compressor damage.

 •  Keep the refrigerant charge below the in-

dicated charge limits if possible. Above this 

limit; protect the compressor against liquid 

flood-back with a pump-down cycle or suc-

tion line accumulator.

 •  Never leave the filling cylinder connected to 

the circuit.

Compressor models

Refrigerant charge 

limit (kg)

SM/SZ 084, 090, 100

8.5

SM/SZ 110, 120

10

SM 112, 124, 147 , SZ147

7.9

SM/SZ 115, 125

11

SM/SZ 148, 160, 161

12.5

SM/SZ 175, 185

13.5

SY/SZ 240

16

SY/SZ 380

20

DSH / SH / WSH 090

5.9

DSH / SH / WSH 105, 120, 

140, 161, 184

7.9

SH 180, 240, 295, 300

13.5

DSH 240,295

15

SH 380

14.5

SH 485, DSH600,  

DSH 381,485

17

Summary of Contents for DSH Series

Page 1: ...ol Spanish p 22 Deutsch German p 27 Portugu s Portuguese p 32 Dansk Danish http instructions cc danfoss com Svenska Swedish Nederlands Dutch Gaeilge Irish Suomi Finnish Lietuviu kalba Lithuanian Latvi...

Page 2: ...e Danfoss scroll compressors DSH SM SY SZ SH DSF WSH scroll compressors used for air conditioning systems They provide necessary information regarding safety and proper usage of this product 70 65 60...

Page 3: ...els except SH380 3 DSH SH WSH140 3 161 3 184 SH380 3 These Danfoss scroll compressors are protected against overheating and overloading by an internal safety motor protector However an external manual...

Page 4: ...gas thermistor embedded in compressors DSH240 600 and SH485 DGT Surface Sump Heater SSH Compressor motor M Motor Protection Module MPM Thermistor chain S Safety pressure switch LPS Thermal magnetic m...

Page 5: ...he circuit with oxygen or dry air This could cause fire or explosion SM 084 to 185 SY 380 SZ 084 to 185 SZ 380 DSH SH WSH 090 to 184 Pressurize the system on HP side first and then on LP side Never le...

Page 6: ...e compressor must be operating during this process Do not overcharge the system Never release refrigerant to atmosphere For reversible systems ensure that the 4 way valve does not reverse when the com...

Page 7: ...d calage maximal par rapport la verticale 15 Toute op ration de montage et d entretien du compresseur doit exclusivement tre effectu e par un personnel qualifi Le montage la mise en service la mainte...

Page 8: ...eurs Danfoss sont prot g s contre la surchauffe et la surcharge par un dispositif interne de protection du moteur Toutefois il est recommand d utiliser un disjoncteur de surcharge r armement manuel ex...

Page 9: ...deux modules externes qui prot gent contre la perte et l inversion de phases la surchauffe et le courant absorb lev L gende Fusibles F1 Contacteur du compresseur KM Pressostat pump down BP Commutateu...

Page 10: ...uveler le test de d tection des fuites 9 D shydratation et tirage au vide Ne jamais utiliser le compresseur pour faire le vide dans le syst me Raccorder une pompe vide c t BP et c t HP Faire le vide d...

Page 11: ...ant ainsi que les conditions de service titre de r f rence pour les inspections ult rieures 15 Maintenance La pression interne et la temp rature de surface sont dangereuses et susceptibles de provoque...

Page 12: ...T C C T0 C T C C T0 C 30 20 25 30 35 40 45 50 55 60 65 70 25 20 15 10 5 0 5 10 15 20 5 30 T C C T0 C T C C T0 C T C C T0 C T C C T0 C 70 65 60 55 50 45 40 Tc C To C SH 5K 35 30 25 20 15 10 5 35 30 25...

Page 13: ...SM SZ 115 125 160 175 185 DSH SH WSH 090 105 120 140 161 184 SM 084 090 100 110 112 120 124 147 148 161 SZ 084 090 100 110 120 147 148 161 DSH SH WSH 140 3 161 3 184 SH380 3 DSH SH WSH 140 3 161 3 18...

Page 14: ...CS CC 2019 01 DSH485 3 F1 KM HP DSH 240 600 SH 485 DGT SSH M MPM S LPS CB SH DSH485 DSH600 SSH CONTROL CIRCUIT LPS UNIT CONTROLLER SEPARATE SUPPLY KM DGT MPM S CB 1 2 3 L1 L3 L2 7 8 9 L1 L3 L3 L2 L2 S...

Page 15: ...E 5 11 5 kg SM SZ 084 090 100 8 5 SM SZ 110 120 10 SM 112 124 147 SZ147 7 9 SM SZ 115 125 11 SM SZ 148 160 161 12 5 SM SZ 175 185 13 5 SY SZ 240 16 SY SZ 380 20 DSH SH WSH 090 5 9 DSH SH WSH 105 120 1...

Page 16: ...16 AN24598649703302zh 000501 8510197P05F Danfoss DCS CC 2019 01 60 1 5 15 100 C 16 Danfoss 17 Danfoss...

Page 17: ...uardano i compressori scroll Danfoss DSH SM SY SZ SH WSH usati nei sistemi per condizionamento d aria Esse forniscono le informazioni necessarie in materia di sicurezza e uso corretto del prodotto R41...

Page 18: ...184 SH380 3 I compressori Danfoss sono protetti da surriscaldamento e sovraccarico grazie a un protettore interno di sicurezza del motore Tuttavia si raccomanda un protettore di sovraccarico esterno m...

Page 19: ...ato nei compressori serie DSH240 600 e SH485 DGT Riscaldatore carter di superficie SSH Motore del compressore M Modulo protezione motore MPM Catena termistore S Pressostato di sicurezza LPS Interrutto...

Page 20: ...Spegnere e isolare l alimentazione principale Vedere sul retro per i dettagli sul cablaggio Tutti i componenti elettrici devono essere selezionati in base agli standard locali ed ai requisiti del com...

Page 21: ...dere le competenze e gli strumenti appropriati La temperatura della tubazione pu superare i 100 C e pu causare bruciature gravi Assicurarsi di eseguire ispezioni periodiche per garantire l affidabilit...

Page 22: ...ricante de f brica 1 Introducci n Estas instrucciones son aplicables a los compresores scroll Danfoss SM SY SZ SH y WSH utilizados para sistemas de aire acondicionado Ofrecen la informaci n necesaria...

Page 23: ...tor contra el exceso de intensidad y temperatura generada por una sobrecarga causada por poca circulaci n de refrigerante p rdida de fase rotaci ndemotorincorrecta Elprotectorsecolocaenelpuntodelaestr...

Page 24: ...descarga instalado en compresores DSH240 600 y SH485 DGT Resistencia de c rter de superficie SSH Motor del compresor M M dulo de protecci n del motor MPM Cadena de termistores S Presostato de segurida...

Page 25: ...os internos 10 Conexiones el ctricas Apague el sistema y corte la alimentaci n de red Consulte el folleto para obtener m s informaci n sobre el cableado Todos los componentes el ctricos deben seleccio...

Page 26: ...conocimientos adecuados La temperatura de los tubos puede superar los 100 C y podr a provocar quemaduras graves Aseg rese de que se realizan inspecciones de mantenimiento peri dicas para garantizar la...

Page 27: ...truktion gilt f r die Danfoss Scroll Verdichter DSH SM SY SZ SH und WSH die f r den Einsatz in Klimaanlagen vorgesehen sind Die Anleitung enth lt die f r Sicherheit und ordnungsgem e Handhabung des Pr...

Page 28: ...H WSH140 3 161 3 184 SH380 3 Diese Danfoss Verdichter sind durch einen eingebauten Motorschutzschalter vor bertemperatur und berlast gesch tzt Um den Kreislauf vor berstrom zu sch tzen wird jedoch ein...

Page 29: ...tet bei den Verdichtern DSH240 600 und SH485 DGT Kurbelwannenheizung SSH Verdichtermotor M Motorschutzmodul MPM Thermistorkette S Sicherheitsdruckschalter LPS Thermomagnetischer Motorschutzschalter CB...

Page 30: ...Betriebsdruck darf die auf dem Verdichter Typenschild angegebenen Werte f r die 1 1 x Ps Niederdruck und 1 x Ps Hochdruckseite nicht bersteigen Beim Auftreten einer Leckage die erforder liche Reparat...

Page 31: ...chter stopped w hrend er sich im Heiz oder K hlbedarf befindet Stop Thermostat Vor dem Verlassen des Installationsstandorts eine allgemeine Inspektion der Anlage Sauberkeit ungew hnliche Ger usche Lec...

Page 32: ...SF utilizados em sistemas de ar condicionado Estas instru es fornecem as informa es necess rias utiliza o adequada e com seguran a deste produto 70 65 60 55 50 45 40 Tc C To C SH 5K SH 30K 35 30 25 20...

Page 33: ...otetor de motor interno de seguran a contra sobreaquecimento e sobrecarga No entanto recomenda se um protetor externo de rearme manual contra sobrecargas de forma a proteger o circuito contra alta cor...

Page 34: ...compressor M M dulo de prote o de motor MPM liga o do termistor S Pressostato de seguran a LPS Disjuntor magn tico t rmico CB SSH CONTROL CIRCUIT LPS UNIT CONTROLLER SEPARATE SUPPLY KM DGT MPM S CB 1...

Page 35: ...uma fuga repare a fuga e repita o teste de dete o de fugas 9 Desidrata o a v cuo Nunca utilize o compressor para purgar o sistema Ligue uma bomba de v cuo a ambos os lados de Baixa Press o e de Alta P...

Page 36: ...ermostato Antes de sair do local de instala o fa a uma inspe o geral da instala o no que diz respeito limpeza ru dos e dete o de fugas Registe o tipo e a quantidade da carga de frigor geno assim como...

Reviews: