Safety Note

To avoid injury of persons and damages to 
the device, it is absolutely necessary to read 
and observe these instructions carefully.

Necessary assembly, start-up, and 
maintenance work must be performed by 
qualified and authorized personnel only.

Prior to assembly and depressurizing the 
system.

Please comply with the instructions of the 
system manufacturer or system operator.

AC 24 V

Connect via safety isolating transformer.

Mounting 

Fix the actuator on the valve

Wiring 

Control signal

Control signal from the controller must be 

connected to terminals Y (input signal) and 

SN (common) on the AME printed board.

Output signal

Output signal from the terminal X can be 

used for indication of the current position. 

Range depends on the DIP switch settings.

Supply voltage

Supply voltage (24 V~ -15 to +10%, 50 Hz) 

must be connected to the terminals SN and SP.

DIP switch settings 

 

Factory settings:

ALL switches are on OFF position!

Note:

 

All combinations of DIP switches are 

allowed. All functions that are selected are 

added consecutively. There is only one logic 

override of functionalities i.e. the switch No.6 

Proportional / 3 point, which sets actuator to 

ignore control signal and works as a “simple” 

3-point actuator.

SW 1: 

U/I 

❹ ①

 

 

Actuator can responde to a voltage or 

current control signal. With switch No.1: U/I 

actuator can be set either to operate with 

a voltage control signal (actuator responds 

to signal between 0 … 10 V), or current 

control signal (actuator responds to signal 

between 0 … 20 mA).

Factory setting

voltage control signal (0 … 10 V).

SW 2: 

2V … 10 / 0V … 10 

❹ ②

 

 

Actuator can be set to response on a 

control signal from 2 V, or 0 V. If the 

actuator is set to current signal than it 

responds to control signal from 4 mA or 

0 mA.

Factory setting is: 

2 … 10V.

SW 3: 

Direct/Inverse 

❹ ③

 

Actuator can be set for spindle to travel 

downwards on decreasing control signal 

(DIRECT), OR for spindle to travel upwards 

on rising control signal (INVERSE).

Factory setting is: 

DIRECT

SW 4: 

---/Sequential 

❹ ④

 

Two actuators can be set to work parallel 

with one control signal. If the SEQUENTIAL 

is set than an actuator responds to split 

control signal (see 0(2) V … 5(6 V) / 

6(6) V … 10 V).

Note: 

This combination works in combination with 

switch No.5: 0(2) V … 5(6 V) / 6(6) V … 10 V

SW 5: 

0(2) V … 5(6 V)/6(6) V … 10 V 

❹ ⑤

  

Note:

 

This function is available if switch No.4:  

--- / Sequential is set.  

Actuator can be set to match the range of the 

control signal:

2 … 6 V  (switch No.2: 2 V … 10) 

0 … 5 V   (switch No.2: 0 V … 10) 

4 … 12 mA  

(switch No.2: 2 V … 10)  

0 … 10 mA  

(switch No.2: 0 … 10)

OR

6 … 10 V  

(switch No.2: 2 V … 10) 

5 … 10 V  

(switch No.2: 0 V … 10) 

12 … 20 mA  

(switch No.2: 2 V … 10)  

10 … 20 mA  

(switch No.2: 0 … 10)

SW 6: 

Proportional/3 point 

❹ ⑥

 

Actuator can operate as “simple” 3-point 

actuator, if the 3-point function is selected. 

Power supply should be connected on 

SN and SP ports. On port 1 or 3 24 VAC 

signal is connected for rising or lowering 

of actuator. Return signal X indicates the 

correct position.

Note:

if 

3 point

 function is selected actuator does 

not respond to any control signal on port Y. 

It only rises and lowers spindle if power is 

supplied on port 1 or 3.

SW 7: 

LOG flow/LIN flow 

❹ ⑦

 

Large AB-QM valve has linear characteristic.  
With setting switch to LIN flow the 
characteristic remains linear. With setting 
switch to LOG flow the characteristic of 
actuator is modified the way that actuator 
and valve work together as valve with LOG 
characteristic.

Factory setting:

LOG. Flow (characteristic of valve is 
unchanged)

SW 8: 

100% K

VS

/RED. K

VS 

❹ ⑧

 

To be set on OFF position.

SW 9: 

Reset 

❹ ⑨

 

After the actuator has been connected to 
power supply, the actuator will start the 
self-adjustment procedure. The indicator LED 
flashes until self adjustment is finished. The 
duration depends on the spindle travel and 
will normally last a few minutes. The stroke 
length of the valve is stored in the memory 
after self adjustment has been completed. To 
restart self adjustment, change the position 
of RESET switch  (switch No.9). If the supply 
voltage is switched off or falls below 80% in 
more than 0.1s, the current valve position will 
be stored in the memory and all data remain 
saved in the memory also after a power 
supply cut-out.

Function test

The indicator light shows whether the 

positioner is in operation or not. Moreover, 

the indicator shows the control status and 

faults.

Constant light

-   normal operation

No light 

-   no operation or no power supply

Intermittent light (1 Hz)  

-   self adjusting-mode

Intermittent light (3 Hz): 

-   power supply too low
-  insufficient valve stroke (<20 s)
-   end-position cannot be reached.

Summary of Contents for AME 55QM

Page 1: ...LANDS AME 55 QM www danfoss nl Bladzijde 10 SUOMEKSI AME 55 QM www danfoss fi Sivu 11 LIETUVI K AME 55 QM www danfoss lt Puslapis 12 ROM N AME 55 QM www danfoss ro Pagina 13 POLSKI AME 55 QM www heati...

Page 2: ...AC 24 V Connect via safety isolating transformer 73691210 DH SMT SI VI CV B1 2N Danfoss 11 2010 2...

Page 3: ...73691210 DH SMT SI VI CV B1 2N Danfoss 11 2010 3...

Page 4: ...ignal see 0 2 V 5 6 V 6 6 V 10 V Note This combination works in combination with switch No 5 0 2 V 5 6 V 6 6 V 10 V SW 5 0 2 V 5 6 V 6 6 V 10 V Note This function is available if switch No 4 Sequentia...

Page 5: ...5 6 V 6 6 V 10 V Bem rk Denne kombination fungerer sammen med omskifter nr 5 0 2 V 5 6 V 6 6 V 10 V SW 5 0 2 V 5 6 V 6 6 V 10 V Bem rk Denne funktion er tilg ngelig hvis omskifter nr 4 sekventiel er i...

Page 6: ...rsignal siehe 0 2 V bis 5 6 V 6 6 V bis 10 V Hinweis Diese Kombination funktioniert mit dem Schalter Nr 5 0 2 V bis 5 6 V 6 6 V bis 10 V SW 5 0 2 V bis 5 6 V 6 6 V bis 10 V Hinweis Diese Funktion steh...

Page 7: ...Si la fonction S QUENTIEL est r gl e le moteur r pond au signal de commande split voir 0 2 V 5 6 V 6 6 V 10 V Remarque Cette combinaison fonctionne en association avec la commande 5 0 2 V 5 6 V 6 6 V...

Page 8: ...AL el actuador responder a una se al de control dividida v ase 0 2 V 5 6 V 6 6 V 10 V Nota Esta combinaci n funciona en combinaci n con el interruptor n 5 0 2 V 5 6 V 6 6 V 10 V SW 5 0 2 V 5 6 V 6 6 V...

Page 9: ...Om SEKVENTIELL st lls in kommer motorn att svara mot en delad styrsignal se 0 2 V 5 6 V 6 6 V 10 V Obs Denna kombination arbetar tillsammans med omkopplare nr 5 0 2 V 5 6 V 6 6 V 10 V SW 5 0 2 V 5 6...

Page 10: ...p een gedeeld signaal NB Deze instelling werkt samen met schakelaar 5 0 2 V 5 6 V 6 6 V 10 V Sleutel 5 0 2 V 5 6 V 6 6 V 10 V NB Deze functie is geldig als schakelaar 4 op Sequential staat De motor ka...

Page 11: ...ytt laite reagoi jaettuun ohjaussignaaliin Lis tietoja on kohdassa 0 2 5 6 V 6 6 10 V Huomautus T m yhdistelm toimii yhdess kytkimen 5 kanssa 0 2 V 5 6 V 6 6 V 10 V SW 5 0 2 V 5 6 V 6 6 V 10 V Huomaut...

Page 12: ...lygiagre iai Jei nustatomas nuoseklusis veikimas SEQUENTIAL pavara reaguoja padalyt valdymo signal r 0 2 V 5 6 V 6 6 V 10 V Pastaba i funkcij reikia derinti su 5 jungikliu 0 2 V 5 6 V 6 6 V 10 V 5 jun...

Page 13: ...semnal de comand Dac este setat SECVEN IAL un servomotor r spunde la semnalul de comand divizat vezi 0 2 V 5 6 V 6 6 V 10 V Not Aceast combina ie lucreaz n leg tur cu comutatorul nr 5 0 2 V 5 6 V 6 6...

Page 14: ...m sygna em steruj cym Je li wybrana jest opcja SEQUENTIAL si ownik reaguje na dzielony sygna steruj cy patrz 0 2 V 5 6 V 6 6 V 10 V Uwaga To ustawienie dzia a w po czeniu zprze cznikiemnr5 0 2 V 5 6V...

Page 15: ...nap t kles Jestli e je nastaven do polohy ON tak pohon pracuje jako inverzn inn inverse v eteno p i rostouc m nap t stoup Tov rn nastaven je P M SW 4 Norm ln nebo sekven n re im Dva servopohony lze na...

Page 16: ...0 0 20 0 10 SW 2 2V 10 0V 10 2 0 4 0 2 10V SW 2 SW 4 0 2 5 6 6 6 10 5 0 2 5 6 6 6 10 SW 5 0 2 V 5 6 V 6 6 V 10 V 4 2 6 V 2 2 10 0 5 V 2 0 10 4 12 mA 2 2 10 0 10 mA 2 0 10 6 10 V 2 2 10 5 10 V 2 0 10 1...

Page 17: ...gy reag l hogy felosztja a vez rl jelet l sd a 0 2 5 6 V 6 6 10 V Megjegyz s Ez a kombin ci az 5 s sz m mikrokapcsol val egy tt m k dik 0 2 V 5 6 V 6 6 V 10 V SW 5 0 2 V 5 6 V 6 6 V 10 V Megjegyz s E...

Page 18: ...U I 0 10 V 0 20 mA 0 10 V SW 2 2V 10 0V 10 2 V 0 V 4 mA 0 mA 2 10V SW 3 SW 4 0 2 V 5 6V 6 6 V 10 V 5 0 2 V 5 6V 6 6 V 10 V SW 5 0 2 V 5 6 V 6 6 V 10 V 4 2 6 V 2 2 V 10 0 5 V 2 0 V 10 4 12 mA 2 2 V 10...

Page 19: ...ontrolnim signalom Ako je pode eno na UZASTOPNO onda jedan pogon reaguje na podeljen kontrolni signal videti 0 2 V 5 6 V 6 6 V 10 V Napomena Ova kombinacija radi u kombinaciji s prekida em br 5 0 2 V...

Page 20: ...tako da delujeta vzporedno z enim regulacijskim signalom Pri nastavljenem parametru SEKVEN NO se pogon odziva na razdeljen regulacijski signal glejte 0 2 V 5 6 V 6 6 V 10 V Opomba Ta kombinacija deluj...

Page 21: ...de al segnale di comando split vedi 0 2 V 5 6 V 6 6 V 10 V Nota Questacombinazionefunzionaassieme all interruttoreN 5 0 2 V 5 6V 6 6 V 10V SW 5 0 2 V 5 6 V 6 6 V 10 V Nota Questa funzione disponibile...

Page 22: ...olsign lu Ja ir iestat ts re ms SEQUENTIAL Sec gs tad izpildmeh nisms rea uz dal tu kontrolsign lu sk 0 2 V 5 6 V 6 6 V 10 V Piez me kombin cija ir piem rota izmantojot 5 sl dzi 0 2 V 5 6 V 6 6 V 10 V...

Page 23: ...23 73691210 DH SMT SI VI CV B1 2N Danfoss 11 2010 23...

Page 24: ...73691210 DH SMT SI VI CV B1 2N Danfoss 11 2010 24...

Reviews: