530
Outside unit multi connection piping kit and
Refrigerant branch kit selection
Pipe size selection
•
Refrigerant branch kits can only be used with R410A.
•
When multi outdoor system are installed, be sure to use the
special separately sold Outside unit multi connection piping
kit. (BHFP22P100U).
(For how to select the proper kit, follow the table at right.)
•
Never use BHFP26M90U, BHFP22M90U for M type of this
series or T joint (field supplyed).
How to select the REFNET joint
Piping between outside unit(*2) and refrigerant branch kit (partA)
How to select the REFNET header
When using REFNET joint at the first branch counted from the outside unit side,
choose from the following table in accordance with the outside unit capacity type.
(Example :REFNET jointA)
Choose from the following table in accordance with the outside units system
capacity type.
Piping between outside unit multi connection piping kit and outside unit (part B)
Choose from the following table in accordance with the capacity type
of the outside unit connected.
Choose form the following table in accordance with the total capacity index of all
the indoor units conncted below the REFNET header.
How to select the outside unit multi connection piping kit
(This is required when the system is multi outside unit system.)
Choose from the following table in accordance with the number of outside units.
Choose the REFNET joints other than the first branch from the following table in a accordance
with the total capacity index of all the indoor units connected below the REFNET joint.
Outside unit capacity type
RXYQ72 · 96P type
RXYQ120 ~ 216P type
RXYQ240P type
Indoor unit total capacity index
× < 72
72
≤
× < 111
111
≤
×
Refrigerant branch kit name
KHRP26M33T
KHRP26M72TU
KHRP26M73TU
Refrigerant branch kit name
KHRP26M22T
KHRP26M33T
KHRP26M72TU
Indoor unit total capacity index
× < 72
72
≤
× < 111
111
≤
×
Number of outside unit
2 units
Connecting piping kit name
BHFP22P100U
Refrigerant branch kit name
KHRP26M22H or KHRP26M33H
KHRP26M33H
KHRP26M72H
Example for indoor units
connected downstream
Example REFNET joint C : Indoor units 5 + 6 + 7 + 8
Example REFNET joint B : Indoor units 7 + 8
Example REFNET header : Indoor units 1 + 2 + 3 + 4 + 5 + 6
Example REFNET header :
indoor units 1 + 2 + 3 + 4 + 5 + 6 + 7 + 8
The thickness and material shall be selected in
accordance with local code.
For an outside unit installation, make
the settings in accordance with the
following figure.
Outside unit
High side equalizer pipe (part C)
Piping between outside unit
multi connection piping kit
and outside unit (part B)
Piping between outside unit multi
connection piping kits
Piping between outside unit and
refrigerant branch kit (part A)
Outside unit
capacity type
RXYQ72P type
RXYQ96P type
RXYQ120P type
RXYQ144P type
RXYQ168P type
RXYQ192 · 216P type
RXYQ240P type
Piping size (O. D.)
Piping size (O. D.)
Gas pipe
φ
3/4
φ
7/8
φ
1-1/8
φ
1-3/8
Liquid pipe
φ
3/8
φ
1/2
φ
5/8
Outside unit
capacity type
RXYQ72P type
RXYQ96P type
RXYQ120P type
Gas pipe
φ
3/4
φ
7/8
φ
1-1/8
Liquid pipe
φ
3/4
φ
1/2
Piping between refrigerant branch kits
Choose from the following table in accordance with the total capacity type
of all the indoor units connected downstream.
Piping between refrigerant branch kit and indoor unit.
High side Equalizer pipe (part C)(outside multi system only)
Match to the size of the connection pipng on the indoor unit.
*1 Connection piping must not exceed the refrigerant Piping size between outside
unit and refrigerant branch kit (part A)
Indoor capacity index
× < 54
54
≤
× < 72
72
≤
× < 111
111
≤
× < 162
162
≤
×
Indoor unit capacity type
07 · 09 · 12 · 18
24 · 30 · 36 · 48
Gas pipe
φ
1/2
φ
5/8
Liquid pipe
φ
1/4
φ
3/8
Piping size (O. D.)
φ
3/4
(unit : in.)
(unit : in.)
Piping size (O. D.)
(unit : in.)
Piping size (O. D.)
(unit : in.)
(unit : in.)
Low side Equalizer pipe (part D)(outside multi system only)
Piping size (O. D.)
φ
3/4
(unit : in.)
Gas pipe
φ
5/8
φ
3/4
φ
7/8
φ
1-1/8
Liquid pipe
φ
3/8
φ
1/2
φ
5/8
Low side equalizer pipe (part D)
Summary of Contents for RXYQ96PYDN
Page 15: ...SiUS34 801A_b xiv...
Page 23: ...Model Selection SiUS34 801A_b 8 General Information...
Page 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Page 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Page 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Page 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Page 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Page 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Page 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Page 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Page 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Page 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Page 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Page 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Page 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Page 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Page 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Page 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Page 563: ...SiUS34 801A_b iv Index...