Troubleshooting by Remote Controller
SiUS34-801A_b
332
Troubleshooting
<Selection of setting item>
<Monitor mode>
<Confirmation of malfunction 1>
To enter the monitor mode, push the
MODE (BS1) button when in
“Setting mode 1”.
Push the SET (BS2) button and set
the LED display to a setting item.
Push the RETURN (BS3) button
once to display "First digit" of
malfunction code.
<Confirmation of malfunction 2>
Push the SET (BS2) button once to
display "Second digit" of malfunction
code.
Push the RETURN (BS3) button and
switches to the initial status of
“Monitor mode”.
∗
Push the MODE (BS1) button and
returns to “Setting mode 1”.
<Confirmation of malfunction 3>
Push the SET (BS2) button once to
display "malfunction location".
* Refer to Page 106, 254 for Monitor
mode.
* Refer to Page 106, 254 for Monitor
mode.
Detail
description
on next
page.
<Confirmation of malfunction 4>
Push the SET (BS2) button once to
display "master or slave 1 or slave 2"
and "malfunction location".
Malfunction code
Malfunctions
Malfunction
code
Description of malfunction
Description of malfunction (PGF)
Remote
controller
PC board malfunction
PC board malfunction
E1
Faulty PC board
Leak detection PC board
Indicate electric leakage detected by
the leak detection PC board
E2
Abnormal discharge pressure
HPS activated
E3
Abnormal suction pressure
Pe malfunction
E4
Compressor lock
INV compressor lock detected
E5
OC activation
STD1 compressor lock detected
E6
STD2 compressor lock detected
Overload, overcurrent and abnormal
lock of outdoor unit fan motor
Instantaneous overcurrent of DC fan motor for fan 1
E7
DC fan motor lock detected for fan 1
Instantaneous overcurrent of DC fan motor for fan 2
DC fan motor lock detected for fan 2
Electronic expansion valve
malfunction
EVM
E9
EV2
EVT
Positioning signal malfunction of
outdoor unit fan motor
DC fan motor positioning signal malfunction for fan 1
H7
DC fan motor positioning signal malfunction for fan 2
Abnormal outdoor temperature
Ta sensor malfunction (short-circuited)
H9
Ta sensor malfunction (open)
Abnormal discharge pipe temperature Td malfunction
F3
Abnormal heat exchanger temperature
Refrigerant overcharged
F6
Current sensor malfunction
CT1 sensor malfunction
J2
CT2 sensor malfunction
Discharge pipe temperature sensor
malfunction
Tdi sensor malfunction (short-circuited)
J3
Tds1 sensor malfunction (short-circuited)
Tds2 sensor malfunction (short-circuited)
Tdi sensor malfunction (open)
Tds1 sensor malfunction (open)
Tds2 sensor malfunction (open)
Heat exchanger gas temperature
sensor malfunction
Tg sensor malfunction (short-circuited)
J4
Tg sensor malfunction (open)
Suction pipe temperature sensor
malfunction
TsA sensor malfunction (short-circuited)
J5
TsA sensor malfunction (open)
Heat exchanger temperature sensor
malfunction
Tb sensor malfunction (short-circuited)
J6
Tb sensor malfunction (open)
Liquid pipe temperature sensor
malfunction 1
Tsc sensor malfunction (short-circuited)
J7
Tsc sensor malfunction (open)
TL sensor malfunction (short-circuited)
TL sensor malfunction (open)
Liquid pipe temperature sensor
malfunction 2
Tf sensor malfunction (short-circuited)
J8
Tf sensor malfunction (open)
Subcool heat exchanger temperature
sensor malfunction
Tsh sensor malfunction (short-circuited)
J9
Tsh sensor malfunction (open)
Discharge pressure sensor malfunction
Pc sensor malfunction (short-circuited)
JA
Pc sensor malfunction (open)
Suction pressure sensor malfunction
Pe sensor malfunction (short-circuited)
JC
Pe sensor malfunction (open)
8
: ON
9
: Blink
1
: OFF
Summary of Contents for RXYQ96PYDN
Page 15: ...SiUS34 801A_b xiv...
Page 23: ...Model Selection SiUS34 801A_b 8 General Information...
Page 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Page 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Page 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Page 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Page 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Page 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Page 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Page 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Page 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Page 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Page 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Page 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Page 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Page 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Page 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Page 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Page 563: ...SiUS34 801A_b iv Index...