Field Settings
SiUS34-801A_b
94
VRVIII R-410A Heat Pump 60Hz
12.Field Settings
12.1 Field Settings on the Outdoor Unit
12.1.1 Field Settings on the Outdoor Unit
List of Field Setting Items
This following section indicates the list of field setting items. For the lists of dip switch contents,
Setting mode 1, and Setting mode 2, refer to information in tables shown on the following page
onward.
For setting items of (*1), refer to detailed information provided on page 101 onward.
Setting item
Content and objective of setting
Overview of setting procedure
Reference
page
Fu
nction setti
n
g
2
Setting of low
noise
operation (*1)
A. Use external input to step down the upper
limit of the fan (factory set to Step 8),
providing low noise level.
(1) Mode 1: Step 5 or lower
(2) Mode 2: Step 4 or lower
(3) Mode 3: Step 3 or lower
Use the [External control adaptor for
outdoor unit".
Set to [External control adaptor for
outdoor unit" with No. 12 of [Setting mode
2] and select the mode with No. 25.
If necessary, set the [Capacity priority
setting] to ON with No. 29.
B. The low noise operation aforementioned
is enabled in nighttime automatic low
noise operation mode.
Start time: Possible to select in the range
of 20:00 to 24:00 hours.
End time: Possible to select in the range
of 06:00 to 08:00 hours.
(Use the said time as a guide since the
start time and the end time are estimated
according to outdoor temperatures.)
Make this setting while in [Setting mode
2].
Select a mode with No. 22 of [
Setting
mode 2
].
Select the start time with No. 26 and the
end time with No. 27.
If necessary, set the [Capacity priority
setting] to ON with No. 29.
3
Setting of
demand
operation (*1)
Used to place limits on the compressor
operating frequency to control the upper
limit of power consumption.
(1) Mode 1 of Demand 1: 60% or less of
rating
(2) Mode 2 of Demand 1: 70% or less of
rating
(3) Mode 3 of Demand 1: 80% or less of
rating
(4) Demand 2: 40% or less of rating
For setting with the use of "external
control adapter":
Set the system to [External control
adaptor for outdoor unit] with [No. 12 of
Setting mode 2] and select the mode with
No. 30.
For setting only in [Setting mode 2] :
Set the system to Normal demand mode
with No. 32 of [Setting mode 2] and
select the mode with No. 30.
4
Setting of
AirNet
address
Used to make address setting with AirNet
connected.
Set the AirNet to an intended address
using binary numbers with No. 13 of
[Setting mode 2] .
6
Setting of
high static
pressure
Make this setting to operate a system with
diffuser duct while in high static pressure
mode. (Use this setting mode when
shields are installed on upper floors or
balconies.)
* In order to mount the diffuser duct,
remove the cover from the outdoor unit
fan.
Set No. 18 of [Setting mode 2] to ON.
7
Prevention of
minute
heating
operation by
heating
thermostat
OFF unit or
non-heating-
operation unit
Make this setting to prevent a rise in room
temperature due to minute heating
capacity generated by heating thermostat
OFF unit or non-heating-operation unit
while in heating operation.
Set the Setting item No. 41 of [Setting
mode 2] to heating thermostat OFF unit or
non-heating-operation unit.
(Overseas unit: Default set to “ON”)
8
Setting of BS
Cool-Heat
selection
control time
Make this setting to shorten the BS Cool-
Heat selection control time.
Set the Setting item No. 42 of [Setting
mode 2] to [
ON
].
Summary of Contents for RXYQ96PYDN
Page 15: ...SiUS34 801A_b xiv...
Page 23: ...Model Selection SiUS34 801A_b 8 General Information...
Page 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Page 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Page 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Page 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Page 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Page 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Page 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Page 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Page 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Page 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Page 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Page 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Page 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Page 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Page 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Page 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Page 563: ...SiUS34 801A_b iv Index...