SiUS34-801A_b
Test Operation
VRVIII R-410A Heat Pump 60Hz
91
Note:
Heating is not possible if the outdoor temperature is 75°F or higher. Refer to the Operation
manual.
If a knocking sound can be heard in the liquid compression of the compressor, stop the unit
immediately and then energize the crank case heater for a sufficient length of time before
restarting the operation.
Once stopping, the compressor will not restart in about 5 minutes even if the On/Off button of
the remote controller is pushed.
When the system operation is stopped by the remote controller, the outside units may continue
operating for further 5 minutes maximum.
The outside unit fan may rotate at low speeds if the Night-time low noise setting or the External
low noise level setting is made, but this is not a malfunction.
If the check operation was not performed at first installation, the malfunction code [
U3
] will be
displayed in the remote controller. Perform the check operation following
[10.2.5.4 Procedure
of Check Operation]
.
10.2.7.3 Checks after Test Run
Perform the following checks after the test run is complete.
Record the contents of field setting.
→
Record them on the accessory
[REQUEST FOR THE INDICATION]
label.
And attach the label on the back side of the front panel.
Record the installation date.
→
Record the installation date on the accessory
[REQUEST FOR THE INDICATION]
label in
accordance with the IEC60335-2-40.
And attach the label on the back side of the front panel.
Note:
After the test run, when handing the unit over to the customer, make sure the Electrical Componets
Box lid, the inspection door, and the unit casing are all attached.
10.3 Operation when Power is Turned On
10.3.1 When Turning On Power First Time
The unit cannot be run for up to 12 minutes to automatically set the master power and address
(indoor-outdoor address, etc.).
Status
10.3.2 When Turning On Power the Second Time and Subsequent
Tap the RESET button on the outdoor unit PC board. Operation becomes possible for about 2
minutes. If you do not push the RESET button, the unit cannot be run for up to 10 minutes to
automatically set master power.
Status
Outdoor unit
Test lamp H2P .... Blinks
Can also be set during operation described above.
Indoor unit
If the
ON
button is pushed during operation described above, the [
UH
]
malfunction indicator blinks.
Returns to normal when automatic setting is complete.
Outdoor unit
Test lamp H2P .... Blinks
Can also be set during operation described above.
Indoor unit
If ON button is pushed during operation described above, the operation lamp
lights but the compressor does not operate. Returns to normal when automatic
setting is complete.
Summary of Contents for RXYQ96PYDN
Page 15: ...SiUS34 801A_b xiv...
Page 23: ...Model Selection SiUS34 801A_b 8 General Information...
Page 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Page 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Page 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Page 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Page 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Page 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Page 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Page 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Page 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Page 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Page 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Page 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Page 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Page 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Page 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Page 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Page 563: ...SiUS34 801A_b iv Index...