SiUS34-801A_b
Troubleshooting by Indication on the Remote Controller
Troubleshooting
407
Troubleshooting
(V2816)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is an
imbalance in
voltages applied to
the inverter in excess of
14V for 460V units or 6V
for 230V units?
(See *2)
NO
Part or wiring defect
After turning the power supply
OFF, check and repair the
main circuit wiring or parts.
(1) Loose or disconnected
wiring between power
supply and inverter
(2) K2 contact disposition,
fusion or contact is poor.
(3) Loose or disconnected
noise filter
Using a device capable of
constant recording of power
supply voltage record
power supply voltage
between 3 phases (L1 ~ L2,
L2 ~ L3, L3~L1) for about
one continuous week.
Open phase
Normalize field cause.
Power supply voltage imbalance
Even if the power supply voltage is not
unbalanced when measuring it, there are
many cases where it gets unbalanced during
nighttime (around 6:00PM to 10:00PM).
No abnormalities are
observed in the power
supply, but the imbalance
in voltage recurs.
Explanation for users
Fix power supply voltage
imbalance.
Replace the inverter PC board.
YES
YES
NO
Is an
imbalance in
supply voltages in
excess of 14V for 460V
units or 6V for
230V units?
(See *1)
Open phase?
<When voltage monitoring is possible:>
∗
1. Measure voltage at the X1M power supply
terminal block.
∗
2. Measure voltage at connector X10A (RED,
WHITE and BLACK wire pins) of the diode
module inside the inverter while the compressor
is running.
∗
In accordance with "notification of inspection results" accompanying spare parts.
Give the user a copy of "notification of inspection results" and leave
it up to him to improve the imbalance.
Be sure to explain to the user that
there is a "power supply imbalance"
for which DAIKIN is not responsible.
measure
YES
NO
Summary of Contents for RXYQ96PYDN
Page 15: ...SiUS34 801A_b xiv...
Page 23: ...Model Selection SiUS34 801A_b 8 General Information...
Page 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Page 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Page 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Page 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Page 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Page 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Page 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Page 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Page 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Page 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Page 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Page 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Page 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Page 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Page 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Page 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Page 563: ...SiUS34 801A_b iv Index...