Troubleshooting by Indication on the Remote Controller
SiUS34-801A_b
358
Troubleshooting
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Turn OFF the power supply,
and then disconnect
compressor lead wire.
Replace the faulty
part.
Replace the faulty
part.
Securely connect
the connectors.
Replace the
earth leakage
detection PC board
(A7P or A9P*
2
).
Insulation fault
Insulation fault
Disconnected
YES
Check the
compressor for insulation
using a megger
tester.
Check the
whole product for
insulation resistance
using a megger
tester.
Check the
connectors of the HPS
line for any
disconnection.
Check the
earth leakage
detection PC board
(A7P or A9P*
2
) for
any broken wire
in it.
Reinstall all wirings.
Turn ON the power supply.
Check
whether there
is continuity between
both X3A ends of
the earth leakage
detection
PC board.
Check whether
there is continuity
between both ends
of HPS.
Normal
No continuity
*
2
No continuity
Replace the earth
leakage detection
PC board (A7P or
A9P*
2
).
Replace the HPS.
It is supposed that ground leakage occurs due to temporary liquid back or accumulation of
refrigerant.
This phenomenon can occur when power fails while in operation or is cut off for an
extended period of time.
*1: It is normal that there is no continuity between both ends of X3A when the power supply
turns OFF and for a period of 9 seconds at maximum after the power supply turns ON.
*2: A7P: RXYQ72, 96, 120PYDN, PTJU
REMQ72, 96, 120PYDN, PTJU
A9P:
REYQ72, 96, 120PYDN, PTJU
RXYQ144PTJU, REYQ144PTJU
Summary of Contents for RXYQ96PYDN
Page 15: ...SiUS34 801A_b xiv...
Page 23: ...Model Selection SiUS34 801A_b 8 General Information...
Page 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Page 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Page 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Page 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Page 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Page 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Page 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Page 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Page 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Page 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Page 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Page 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Page 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Page 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Page 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Page 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Page 563: ...SiUS34 801A_b iv Index...