Troubleshooting by Indication on the Remote Controller
SiUS34-801A_b
428
Troubleshooting
Troubleshooting
NO
NO
YES
YES
NO
NO
YES
Connect the power supply wire
for the external control adaptor
for outdoor unit to 5V supply line.
Replace the main PC board of
the outdoor unit.
YES
Replace the main PC board of
the outdoor unit.
NO
NO
YES
Set the cooling/heating switch of
the external control adaptor for
outdoor unit to “individual”.
Switch cooling/heating in
a lump.
Setting of
cooling/heating switch
for the external control adaptor
for outdoor unit is “Master
in a lump”.
Setting of
cooling/heating switch
for the external control adaptor
for outdoor unit is “Slave
in a lump”.
Check if
the normal condition
monitor LED for the outdoor
unit main PC board
blinks.
Check if the
outdoor unit is powered on.
Check
if the power supply
wire for the external control adaptor
for outdoor unit is connected
to 5V supply
line.
Check
if the normal
condition monitor LED for
the external control adaptor
for outdoor unit
blinks.
Set
the cooling/heating
switch of the external control
adaptor for outdoor unit to “individual”.
Then check if the failure
occurs again.
YES
NO
The integrated addresses for
cooling/heating within the
outdoor/outdoor transmission are
duplicated. Set the address
again.
NO
YES
Replace the main PC board of
the outdoor unit.
Diagnosis Flow 2
YES
Replace the PC board of the
external control adaptor for
outdoor unit.
Supply power to the outdoor
unit.
Check 3
Check 4
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for RXYQ96PYDN
Page 15: ...SiUS34 801A_b xiv...
Page 23: ...Model Selection SiUS34 801A_b 8 General Information...
Page 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Page 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Page 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Page 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Page 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Page 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Page 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Page 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Page 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Page 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Page 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Page 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Page 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Page 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Page 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Page 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Page 563: ...SiUS34 801A_b iv Index...