Refrigerant Flow for Each Operation Mode
SiUS34-801A_b
40
VRVIII R-410A Heat Pump 60Hz
Operation of refrigerant regulator
1. Recovery of refrigerant
Surplus refrigerant is recovered to refrigerant regulator by opening of SVL and SVG when the
indoor unit load is small.
2. Discharge of refrigerant
Refrigerant is discharge from the refrigerant regulator by opening of SVC when the load of the
outdoor unit is large.
3. Pressure regulating valve (Refrigerant regulator)
The circuit will be closed when SVL, SVO, SVG are all closed. In this case, the increased
pressure in the refrigerant regulator will be transferred to the liquid refrigerant pipe side, to
regulate the pressure.
Suction Pipe
Liquid
Pipe
Equalizing
Pipe
Refrigerant
Regulator
Right
S1NPH
S2NPL
S1PH
EVM
EVT
Tdi
Tb
Tg
Tsc
Tsh
TL
SVP
20SA
SVE
TS_A
Tf
SVL
Pressure
regulating valve
SVO
SVG
Ta
INV
Pressure
regulating valve
Suction Pipe
Liquid
Pipe
Equalizing
Pipe
Refrigerant
Regulator
Right
S1NPH
S2NPL
S1PH
EVM
EVT
Tdi
Tb
Tg
Tsc
Tsh
TL
SVP
20SA
SVE
TS_A
Tf
SVL
SVO
SVG
Ta
INV
Summary of Contents for RXYQ96PYDN
Page 15: ...SiUS34 801A_b xiv...
Page 23: ...Model Selection SiUS34 801A_b 8 General Information...
Page 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Page 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Page 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Page 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Page 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Page 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Page 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Page 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Page 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Page 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Page 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Page 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Page 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Page 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Page 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Page 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Page 563: ...SiUS34 801A_b iv Index...