SiUS34-801A_b
Field Setting
VRVIII R-410A Heat Recovery 60Hz
265
<REYQ72 to 120PYDN, REYQ72 to 144PTJU>
8
Disabling the compressor 1 (on the right side) from operating:
Set No. 38 of setting mode 2 to
Disable-compressor-1 operation
8
Disabling the compressor 2 (on the left side) from operating:
Set No. 39 of setting mode 2 to
Disable-compressor-2 operation
.
<REYQ144 to 240PYDN, REYQ168 to 240PTJU>
Make disable-operation setting by each outdoor unit.
Make the following setting on the outdoor unit 1. (If this setting is made on an outdoor unit other
than the outdoor unit 2, the setting will become invalid.)
* It is possible to tell the outdoor units 1 and 2 according the LED displays shown below.
8
Disabling the outdoor unit 1 to operate:
Set No. 38 of setting mode 2 to
Disable-outdoor-unit-1operation
.
8
Disabling the outdoor unit 2 from operating:
Set No. 39 of setting mode 2 to
Disable-outdoor-unit-2 operation
.
LED display (
8
: ON,
1
: OFF,
9
: Blink)
(Step)
H1P-----------H7P
(1) Press and hold the
MODE
button (BS1)
for 5 sec. or more.
8111111
(2) Press the
SET
button (BS2) 38 times.
8811881
(3) Press the
RETURN
button (BS3) once.
8111119
(Factory setting)
(4) Press the
SET
button (BS2) once.
8111191
(5) Press the
RETURN
button (BS3) twice.
8111111
(6) Press the
MODE
button (BS1) once.
1181111
LED display (
8
: ON,
1
: OFF,
9
: Blink)
(Step)
H1P-----------H7P
(1) Press the
MODE
button (BS1) for 5
seconds or more.
8111111
(2) Press the
SET
button (BS2) 39 times.
8811888
(3) Press the
RETURN
button (BS3) once.
8111119
(Factory setting)
(4) Press the
SET
button (BS2) once.
8111191
(5) Press the
RETURN
button (BS3) twice.
8111111
(6) Press the
MODE
button (BS1) once.
1181111
LED display (
8
: ON,
1
: OFF,
9
: Blink)
H1P-----------H7P H8P
Outdoor unit 1:
1181111 8
Outdoor unit 2:
1111111 9
LED display (
8
: ON,
1
: OFF,
9
: Blink)
(Step)
H1P-----------H7P
(1) Press and hold the
MODE
button (BS1)
for 5 sec. or more.
8111111
(2) Press the
SET
button (BS2) 38 times.
8811881
(3) Press the
RETURN
button (BS3) once.
8111119
(Factory setting)
(4) Press the
SET
button (BS2) once.
8111191
(5) Press the
RETURN
button (BS3) twice.
8111111
(6) Press the
MODE
button (BS1) once.
1181111
LED display (
8
: ON,
1
: OFF,
9
: Blink)
(Step)
H1P-----------H7P
(1) Press the
MODE
button (BS1) for 5
seconds or more.
8111111
(2) Press the
SET
button (BS2) 39 times.
8811888
(3) Press the
RETURN
button (BS3) once.
8111119
(Factory setting)
(4) Press the
SET
button (BS2) once.
8111191
(5) Press the
RETURN
button (BS3) twice.
8111111
Summary of Contents for RXYQ96PYDN
Page 15: ...SiUS34 801A_b xiv...
Page 23: ...Model Selection SiUS34 801A_b 8 General Information...
Page 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Page 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Page 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Page 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Page 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Page 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Page 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Page 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Page 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Page 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Page 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Page 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Page 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Page 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Page 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Page 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Page 563: ...SiUS34 801A_b iv Index...