Heater Control (Optional PC Board KRP1B ... is required.)
Indoor Unit
295
8. Heater Control (Optional PC Board KRP1B ... is
required.)
The heater control is conducted in the following manner.
[Normal control]
While in heating operation, the heater
control (ON/OFF) is conducted as shown
on the right.
[Overload control]
When the system is overloaded in
heating operation, the heater will be
turned OFF in the following two
manners:
(1) The heater control (ON/OFF) is
conducted through the liquid pipe
temperature (R2T) of the indoor
unit.
(2) The heater control (ON/OFF) is
conducted by converting the
heater temperature into the
condensing pressure equivalent
saturated temperature (Tc)
according to the temperature
detection through the high
pressure sensor (SINPH) of the outside unit.
[Fan residual operation]
While the heater turns OFF, in order to prevent the activation of the thermal protector, the fan
conducts residual operation for a given period of time after the heater turns OFF. This operation is
conducted regardless of with or without heater equipped.
Residual operation time = 100 seconds on ceiling suspended type or 60 seconds on other types
ON
Set temperature
OFF
3.6ºF
3.6ºF
ON
109.4ºF
122ºF Liquid pipe temperature
OFF
ON
122ºF
140ºF
OFF
Condensing pressure
equivalent saturated
temperature
Summary of Contents for RXYQ96PYDN
Page 15: ...SiUS34 801A_b xiv...
Page 23: ...Model Selection SiUS34 801A_b 8 General Information...
Page 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Page 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Page 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Page 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Page 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Page 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Page 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Page 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Page 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Page 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Page 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Page 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Page 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Page 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Page 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Page 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Page 563: ...SiUS34 801A_b iv Index...