SiUS34-801A_b
Troubleshooting by Indication on the Remote Controller
Troubleshooting
385
3.31
J8
Outdoor Unit: Malfunction of Liquid Pipe Thermistor 2
(R7T or R15T)
Remote
Controller
Display
J8
Applicable
Models
RXYQ72P~240PYDN, PTJU
REYQ72P~240PYDN, PTJU
Method of
Malfunction
Detection
Malfunction is detected according to the temperature detected by liquid pipe thermistor.
Malfunction
Decision
Conditions
When the liquid pipe thermistor is short circuited or open.
Supposed
Causes
Faulty liquid pipe thermistor 2 (R7T or R15T)
Faulty outdoor unit PC board
Defect of thermistor connection
Troubleshooting
∗
Refer to “Thermistor Resistance / Temperature Characteristics” table on P523.
(V3075)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the
resistance
measured after
removing the thermistor
(R7T or R15T) from outdoor
unit PC board normal?
(1.8k
Ω
to
800k
Ω
)
Replace outdoor unit PC board
(A1P).
Connect the connector and
operate unit again.
NO
NO
Replace thermistor (R7T or R15T).
YES
YES
Is
the connector
for liquid pipe
thermistor connected to
X30A on outdoor
unit PC board
(A1P)?
Confirm which thermistor is
abnormal using outdoor unit
"monitor mode".
(Refer to P334~335)
Summary of Contents for RXYQ96PYDN
Page 15: ...SiUS34 801A_b xiv...
Page 23: ...Model Selection SiUS34 801A_b 8 General Information...
Page 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Page 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Page 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Page 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Page 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Page 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Page 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Page 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Page 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Page 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Page 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Page 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Page 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Page 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Page 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Page 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Page 563: ...SiUS34 801A_b iv Index...