Troubleshooting by Indication on the Remote Controller
Troubleshooting
377
3.24
H9
Outdoor Unit: Malfunction of Thermistor (R1T) for
Outdoor Air
Remote
Controller
Display
H9
Applicable
Models
RXYQ72P~240PYDN, PTJU
REYQ72P~240PYDN, PTJU
Method of
Malfunction
Detection
Temperature detected by the outdoor air thermistor.
Malfunction
Decision
Conditions
When the outside air temperature thermistor has short circuit or open circuit.
Supposed
Causes
Defective thermistor connection
Defect of thermistor (R1T) for outdoor air
Defect of outdoor unit PC board (A1P)
Troubleshooting
∗
Refer to the
Thermistor Resistance / Temperature Characteristics
table on Page 523.
(V3070)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Resistance
is normal when
measured after
disconnecting the thermistor
(R1T) from the outdoor
unit PC board.
(1.8k
Ω
to
800k
Ω
)
Connector is
connected to X18A of
outdoor PC board
(A1P).
Replace outdoor unit PC board
(A1P).
Connect the connector and turn on
again.
NO
NO
Replace the thermistor (R1T)
YES
YES
Confirm which thermistor is
abnormal using outdoor unit
"monitor mode".
(Refer to P334~335)
Summary of Contents for RXYQ96PYDN
Page 15: ...SiUS34 801A_b xiv...
Page 23: ...Model Selection SiUS34 801A_b 8 General Information...
Page 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Page 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Page 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Page 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Page 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Page 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Page 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Page 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Page 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Page 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Page 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Page 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Page 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Page 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Page 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Page 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Page 563: ...SiUS34 801A_b iv Index...