SiUS34-801A_b
Basic Control
VRVIII R-410A Heat Recovery 60Hz
189
*
1 and 2 : Refer to
Chapter 6:
Control of Electonic Expansion Valve
6.2
Compressor PI Control
Compressor PI Control
Carries out the compressor capacity PI control to maintain Te at constant during cooling operation
and Tc at constant during heating operation to ensure stable unit performance.
[Cooling operation]
[Heating operation]
Rotation of outdoor units
In order to make operating time equal for each compressor of multi connection outdoor units,
outdoor units are used in rotation.
However this is not applicable to single units.
[Rotation of outdoor units]
For multiple outdoor units, an operational priority order is assigned to each outdoor unit on the
control purpose.
The operational priority orders of each outdoor unit are switched by means of outdoor unit rotation.
[System with two outdoor units]
[Timing of outdoor rotation]
In start of startup control
BS unit actuator
Electric
symbol
Normal cooling
Normal heating / Normal simultaneous Cooling /
Heating operation
Electronic expansion valve (EVH)
Y4E
760 pls (fully opened)
760 pls (fully opened)
Electronic expansion valve (EVL)
Y5E
760 pls (fully opened)
0 pls
Electronic expansion valve (EVHS)
Y2E
480 pls (fully opened)
480 pls (fully opened)
Electronic expansion valve (EVLS)
Y3E
480 pls (fully opened)
0 pls
Electronic expansion valve (EVSC)
Y1E
0 pls
0 pls (simultaneous Cooling / Heating operation : PI control)
Controls compressor capacity to adjust Te to
achieve target value (TeS).
Te : Low pressure equivalent saturation temperature
(°F)
Te set value (Make this setting while in Setting
mode 2.)
TeS : Target Te value
(Varies depending on Te setting, operating
frequency, etc.)
*On multi-outdoor-unit systems, this control is made
according to values of the first-priority unit, which is
detected with the pressure sensor.
Te setting
L
M (Normal)
(factory
setting)
H
37
43
45 46 48 50 52
Controls compressor capacity to adjust Tc to
achieve target value (TcS).
Tc : High pressure equivalent saturation temperature
(°F)
Te set value (Make this setting while in Setting
mode 2.)
TcS : Target Tc value
(Varies depending on Tc setting, operating
frequency, etc.)
*On multi-outdoor-unit systems, this control is made
according to values of the first-priority unit, which is
detected with the pressure sensor.
Tc setting
L
M (Normal)
(factory
setting)
H
109
115
118
Outdoor Unit 1
Outdoor Unit 2
Previous time
Priority 1
Priority 2
This time
Priority 2
Priority 1
Next time
Priority 1
Priority 2
Summary of Contents for RXYQ96PYDN
Page 15: ...SiUS34 801A_b xiv...
Page 23: ...Model Selection SiUS34 801A_b 8 General Information...
Page 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Page 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Page 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Page 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Page 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Page 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Page 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Page 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Page 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Page 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Page 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Page 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Page 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Page 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Page 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Page 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Page 563: ...SiUS34 801A_b iv Index...