SiUS34-801A_b
Field Settings
VRVIII R-410A Heat Pump 60Hz
103
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory set
0
Digital pressure
gauge kit display
8
7
7
7
7
7
7
Address
0
8777777
∗
Binary number
1
8777778
(4 digits)
~
15
8778888
1
Cool / Heat
Unified address
8
7
7
7
7
7
8
Address
0
8777777
∗
Binary number
1
8777778
(6 digits)
~
31
8788888
2
Low noise/demand
address
8
7
7
7
7
8
7
Address
0
8777777
∗
Binary number
1
8777778
(6 digits)
~
31
8788888
3
Test operation
8
7
7
7
7
8
8
Test operation: OFF
8777778
∗
Test operation: ON
8777787
5
Indoor forced fan H
8
7
7
7
8
7
8
Normal operation
8777778
∗
Indoor forced fan H
8777787
6
Indoor forced
operation
8
7
7
7
8
8
7
Normal operation
8777778
∗
Indoor forced operation
8777787
8
Te setting
8
7
7
8
7
7
7
Low (Level L)
8777778
Normal (Level M)
8777787
∗
High
N
8777788
High
O
8777877
High
P======
(Level H)
8777878
High
Q
8777887
High
R
8777888
9
Tc setting
8
7
7
8
7
7
8
Low
8777778
Normal (factory setting)
8777787
∗
High
8777877
10
Defrost changeover
setting
8
7
7
8
7
8
7
Slow defrost
8777778
Normal (factory setting)
8777787
∗
Quick defrost
8777877
11
Sequential operation
setting
8
7
7
8
7
8
8
OFF
8777778
ON
8777787
∗
12
External low noise/
demand setting
8
7
7
8
8
7
7
External low noise/demand:
NO
8777778
∗
External low noise/demand:
YES
8777787
13 Airnet address
8
7
7
8
8
7
8
Address
0
8777777
∗
Binary number
1
8777778
(6 digits)
~
63
8888888
18
High static pressure
setting
8
7
8
7
7
8
7
High static pressure setting:
OFF
8777778
∗
High static pressure setting:
ON
8777787
20
Additional refrigerant
charging operation
setting
8
7
8
7
8
7
7
Refrigerant charging: OFF
8777778
∗
Refrigerant charging: ON
8777787
21
Refrigerant
recovery/vacuuming
mode setting
8
7
8
7
8
7
8
Refrigerant recovery / vacuuming: OFF
8777778
∗
Refrigerant recovery / vacuuming: ON
8777787
Summary of Contents for RXYQ96PYDN
Page 15: ...SiUS34 801A_b xiv...
Page 23: ...Model Selection SiUS34 801A_b 8 General Information...
Page 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Page 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Page 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Page 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Page 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Page 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Page 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Page 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Page 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Page 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Page 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Page 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Page 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Page 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Page 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Page 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Page 563: ...SiUS34 801A_b iv Index...