Installation
Si39-406
46
General Information
3.2.9 Drain Piping for Each Model
Ceiling Mounted
Cassette Type
(FXFQ-M Multi-
flow)
1. Rig drain piping
Note:
Lay pipes so as to ensure that drainage can occur with no problems.
Employ a pipe with either the same diameter or with the diameter larger (excluding the raising section) than
that of the connecting pipe (PVC pipe, nominal diameter 25 mm, outside diameter 32 mm).
Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air pockets from
forming.
If the drain hose cannot be sufficiently set on a slope, execute the drain raising piping.
To keep the drain hose from sagging, space hanging wires every 40 to 60 inches.
1/100 gradient or more
3.28~4.92 ft
Fig. 18
GOOD
Hanger bracket
Fig. 19
WRONG
n
n
n
n
n
n
•
•
n
•
n
n
n
Use the attached drain hose (1) and clamp (2).
Insert the drain hose into the drain socket up to the base, and tighten the clamp securely within the portion
of a white tape of the hose-inserted tip. Tighten the clamp until the screw head is less than 3/16" from the
hose.
Wrap the attached sealing pad (10) over the clamp and drain hose to insulate.
Make sure that heat insulation work is executed on the following 2 spots to prevent any possible water leak-
age due to dew condensation.
Indoor drain pipe
Drain socket
<PRECAUTIONS FOR DRAIN RAISING PIPING>
Install the drain raising pipes at a height of less than 21 5/8".
n
Install the drain raising pipes at a right angle to the indoor unit and no more than 11 13/16" from the unit.
Clamp (2)
Tape (White)
Drain hose (1)
Fig. 20
Clamp (2)
Large sealing pad
(10)
(attached)
(attached)
≤
3/16"
Fig. 21
Ceiling slab
Clamp (attached) (2)
Drain raising pipe
Raising section
Drain hose (attached) (1)
≤
29 1/2"
Hanger bracket
Adjustable
(
≤
21 5/8")
3.28~4.92 ft
≤
11 13/16"
7 7/8"
Fig. 22
To ensure no excessive pressure is applied to the included drain hose (1), do not bend or twist when install-
ing. (This may cause leakage.)
If converging multiple drain pipes, install according to the procedure shown below.
Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.
≥
3 15/16"
T-joint converging drain pipes
Slope downwards at a gradient
of at least 1/100
Fig. 23
n
n
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...