Si39-406
Test Operation
General Information
81
No.
Setting item
Description
0
EMG (Emergency
operation 1)
Operates by Standard compressor only when inverter
compressor malfunctions. Temporary operation until the
compressor is replaced. Since the comfortability is extremely
deteriorated, immediately replace the compressor. (This
setting is not applicable to REYQ5M.)
1
—
—
2
Low noise/demand
address
Address for low noise/demand operation
5
Indoor unit forced
fan H
Allows forced operation of indoor unit fan while unit is
stopped. (H tap)
6
Indoor unit forced
operation
Allows forced operation of indoor unit.
8
Te setting
Target evaporation temperature for cooling
9
Tc setting
Target condensation temperature for heating
10
Defrost changeover
setting
Changes the temperature condition for defrost and sets to
quick defrost or slow defrost.
11
Sequential
operation setting
Sets sequential operation
12
External low noise
setting / Demand
setting
Reception of external low noise or demand signal
13
AIRNET address
Set address for AIRNET.
18
High static pressure
setting
Make this setting in the case of operating in high static
pressure mode with diffuser duct mounted.
19
Emergency
operation
(STD compressor
operation
prohibited)
Used to operate system only with inverter compressor when
STD compressor malfunctions. This is a temporary operation
extremely impairing comfortable environment. Therefore,
prompt replacement of the compressor is required.
(This operation, however, is not set with REYQ5M.)
20
Additional
refrigerant charge
operation setting
Carries out additional refrigerant charge operation.
21
Refrigerant
collection mode
setting
Sets to refrigerant collection mode.
22
Night-time low
noise setting
Sets automatic nighttime low noise operation in a simple
way.
The operating time is based on “Starting set” and “Ending
set”.
25
Low noise setting
Sets low noise level when the low noise signal is input from
outside.
26
Night-time low
noise control
starting setting
Sets starting time of nighttime low noise operation.
(Nighttime low noise setting is also required.)
27
Night-time low
noise control
ending setting
Sets ending time of nighttime low noise operation. (Nighttime
low noise setting is also required.)
28
Power transistor
check mode
∗
Check after
disconnection of
compressor wires
Used for trouble diagnosis of DC compressor. Since the
waveform of inverter is output without wiring to the
compressor, it is convenient to probe whether the trouble
comes from the compressor or PC board.
29
Capacity
precedence setting
If the capacity control is required, the low noise control is
automatically released by this setting during carrying out low
noise operation and nighttime low noise operation.
30
Demand setting 1
Changes target value of power consumption when demand
control 1 is input.
32
Normal demand
setting
Normally enables demand control 1 without external input.
(Effective to prevent a problem that circuit breaker of small
capacity is shut down due to large load.
b. “Setting mode 2”
<Selection of setting items>
<Selection of setting conditions>
Push and hold the MODE button
(BS1) for 5 seconds and set to
“Setting mode 2”.
Push the SET button (BS2) and set
the LED display to a setting item
shown in the table on the right.
↓
Push the RETURN button (BS3) and
decide the item. (The present setting
condition is blinked.)
Push the SET button (BS2) and set
to the setting condition you want.
↓
Push the RETURN button (BS3) and
decide the condition.
Push the RETURN button (BS3) and
set to the initial status of “Setting
mode 2”.
∗
If you become unsure of how to
proceed, push the MODE button
(BS1) and return to setting mode 1.
(V2764)
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...