![background image](http://html1.mh-extra.com/html/daikin/reyq96mtju/reyq96mtju_design-installation-and-testing-instruction_4175824058.webp)
Installation
Si39-406
52
General Information
Floor Standing
Type
(FXLQ-M)
Concealed Floor
Standing Type
(FXNQ-M)
Rig the drain pipe as shown below and take measures against condensate. Improperly
rigged piping could lead to leaks and eventually wet furniture and belongings.
(1) Carry out the drain piping
Connect the drain hose (1) using the attached hose and parts, as shown in the right drawing.
If converging multiple drain pipes, install according to the procedure shown below.
Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.
(2) After piping work is finished, check drainage flows smoothly.
Add approximately 1 liter of water slowly from the air outlet and check drainage flow.
(3) Be sure to insulate all indoor pipes
Caution
Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of
ammonia. The ammonia in the sewage might enter the indoor unit through the drain pipes and
corrode the heat exchanger.
Keep in mind that it will become the cause of getting drain pipe blocked if water collects on drain
pipe.
3/4 drain pipe
2 or more
Drip pan
Metal clamp
(accessory) (2)
Drain hose
(accessory) (1)
Cut to suitable length
(length : in.)
Piping process
inside unit
Tilt
Slope downwards at a gradient
of at least 1/100
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...