Installation
Si39-406
18
General Information
Note:
Above figure means minimum value. Please keep these value at least.
Note:
Above figure means minimum value. Please keep these value at least.
Unit (Inch)
FXAQ-M type
≥
2
≥
2
[ Space required for installation (in.) ]
≥
3 1/2
≥
1 1/4
Floor
Obstruction
≤
4 3/4
≥
100 (from floor)
For installation
in high places.
Unit (Inch)
FXLQ-M, FXNQ-M type
Base
FXLQ
Window
4 or
more
(FXLQ)
6 or
more
(FXNQ)
4 or
more
(FXLQ)
3/4 or
more
40 or
more
70 or
more
Air flow direction
Air inlet
direction
Front side
(length : in.)
FXNQ
Maintenance
area
3 1/8 or
more
A or m
ore
B or more
24 5/8
(length :in.)
(IMPORTANT) Leave sufficient clearance for air inlet and maintenance.
Model
A (in.)
B (in.)
FXNQ12MVJU
28
46
FXNQ18 · 24MVJU
39
57
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...