![background image](http://html1.mh-extra.com/html/daikin/reyq96mtju/reyq96mtju_design-installation-and-testing-instruction_4175824071.webp)
Si39-406
Test Operation
General Information
65
4.1.4 Confirmation on normal operation
•
Conduct normal unit operation after the check operation has been completed.
(When outdoor air temperature is 75ºF or higher, the unit can not be operated with heating
mode. See the instruction manual attached.)
Confirm that the indoor/outdoor units can be operated normally.
(When an abnormal noise due to liquid compression by the compressor can be heard, stop the
unit immediately, and turn on the crankcase heater to heat up it sufficiently, then start operation
again.)
•
Operate indoor unit one by one to check that the corresponding outdoor unit operates.
•
Confirm that the indoor unit discharges cold air (or warm air).
•
Operate the air direction control button and flow rate control button to check the function of the
devices.
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...