Refrigerant Piping
Si39-406
170
Installation Manual REYQ96MTJU
Note:
Where a single refrigerant facility is divided into 2 entirely independent refrigerant systems then
use the amount of refrigerant with which each separate system is charged.
2. Calculate the smallest room volume (ft
3
)
In case like the following, calculate the volume of (A), (B) as a single room or as the smallest
room.
A. Where there are no smaller room divisions
B. Where there is a room division but there is an opening between the rooms sufficiently
large to permit a free flow of air back and forth.
(Where there is an opening without a door or where there are openings above and below the
door which are each equivalent in size to 0.15% or more of the floor area.)
3. Calculating the refrigerant density using the results of the calculations in steps 1 and 2 above.
If the result of the above calculation exceeds the maximum concentration level then make
similar calculations for the second then third smallest room and so until the result falls short of
the maximum concentration.
4. Dealing with the situations where the result exceeds the maximum concentration level.
Where the installation of a facility results in a concentration in excess of the maximum
concentration level then it will be necessary to revise the system.
Please consult your Daikin supplier.
1
2
1. opening between rooms
2. partition
total volume of refrigerant in the
refrigerant system
≤
maximum concen-
tration level (Ib./ft
3
)
size (ft
3
) of smallest room in which
there is an indoor unit installed
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...