Si39-406
Refrigerant Piping
Installation Manual REYQ96MTJU
161
7.4
Examples
System example
Field line
connection
L1, L2, L3, phase of the power supply wiring should be clamped to the safetycatch using the
included clamp material.
The green and yellow striped wrapped wires should be used for grounding.
1. Field power supply
2. Main switch
3. Earth leak detector
4. Fuse
5. Cool / heat selector
6. Remote controller
7. Outdoor unit
8. BS unit
9. Indoor unit
power supply wiring
(sheathed cable)
transmission wiring
(sheathed cable)
1
2
3
8
5
3
4
4
7
6
9
5
L 1
L 2
L 3
1
3
2
4
6
7
14
13
15
16
17
8
9
10
11
12
1. Power supply
(208~230 V, Three-phase)
2. Branch switch, overcurrent breaker
3. Grounding wire
4. Earth leakage breaker
5. Section A
6. Attach insulation sleeves.
7. Power supply terminal block
8. Grounding terminal
9. Retain the ground wire along with the power
supply wiring accessory clamps (1).
10. Retain the power supply wiring to the bracket
using the accessory clamps (1).
11. Grounding wire
12. When wiring, do not allow the ground wire to
contact the compressor lead wires. If the wire
contacts each other, adverse effects may occur
to other units.
13. When connecting two wires to one terminal,
ensure that the crimp-style terminals face with
each other back to back.
Moreover, make sure that the wire of the
smaller gauge is located above.
14. Terminal block
15. Crimp-style terminal
16. Wire gauge: Small
17. Wire gauge: Large
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...