Installation
Si39-406
60
General Information
Caution in installation
1. Execute the installation work by checking the foundation strength and levelness to avoid any occurrence of
vibration and noise.
Fix the unit tightly with foundation bolts. (Prepare 4 sets of M12 foundation bolts with proper nuts and
washers.)
The proper length of the foundation bolts form the surface of the base is 13/16".
Caution
Install the unit securely in case of earthquake an typhoon, cyclone, hurricane or other strong wind. The unit
may topple or cause another accident if improperly set up.
Unpacking and
Placing the Unit
Make sure the unit is installed level on a sufficiently strong base to prevent vibration and noise.
Secure the unit to its base using foundation bolts. (Use four commercially available M12-type
foundation bolts, nuts, and washers.)
The foundation bolts should be inserted 13/16".
Make sure the base under the unit extended more than 30 1/8" behind the unit.
The height of the base should be at least 5 7/8" from the floor.
The unit must be installed on a solid longitudinal foundation (steelbeam frame or concrete) as
indicated in the figure below.
DO NOT USE STANDS TO SUPPORT THE CORNERS
Note:
1. Prepare a water drainage channel around the foundation to condensate waste water from
around the unit.
2. If the unit is to be installed on a roof, check the strength of the roof and its drainage facilities
first.
3. If the unit is to be installed on a frame, install the waterproofing board within a distance of 5 14/
16" under the unit in order to prevent infiltration of water coming from under the unit.
Model
A (in.)
B (in.)
Q96 type
48 13/16
43 3/8
13/16
”
28 7/16 - 29
3 1/8
3 1/8
30 1/8
A
B
1
2
3
(in.)
1. Foundation bolt point (
φ
9/16"
dia. : 4 positions)
2. Depth of product
3. Shape of indoor unit’s support
leg and foundation bolt
positions
1
1. Do not use stands to
support the corners.
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...