Refrigerant Piping
Si39-406
154
Installation Manual REYQ96MTJU
Opening shutoff
valve
1. Remove the cap and turn the valve counterclockwise with the hexagon wrench.
2. Turn it until the shaft stops.
Do not apply excessive force to the shutoff valve. Doing so may break the valve body, as the
valve is not a backseat type. Always use the special tool.
3. Make sure to tighten the cap securely.
Closing shutoff
valve
1. Remove the cap and turn the valve clockwise with the hexagon wrench.
2. Securely tighten the valve until the shaft contacts the main body seal.
3. Make sure to tighten the cap securely.
•
For the tightening torque, refer to the table below.
Tightening torque
CAUTION
Always use a charge hose for service port connection.
After tightening the cap, check that no refrigerant leaks are present.
When loosening a flare nut, always use two wrenches in combination.
When connecting the piping, always use a spanner and torque wrench in combination to tighten
the flare nut.
When connecting a flare nut, coat the flare (inner and outer faces) with ether oil or ester oil and
hand-tighten the nut 3 to 4 turns as the initial tightening.
Shutoff
valve size
Tightening torque ft.-Ibf (Turn clockwise to close)
Shaft (valve body)
Cap
(valve lid)
Service
port
Flare nut
Suction gas
line piping
attached to unit
(1)
φ
3/8"
3.98-4.87
Hexagon
wrench
0.16 in.
9.96-12.17
8.48-10.25
24.1-29.4
—
φ
3/4"
9.96-12.17
Hexagon
wrench
0.24 in.
17.33-20.28
71.55-87.77
—
φ
7/8"
19.91-24.34
Hexagon
wrench
0.39 in.
26.55-32.45
—
16.23-20.65
1
2
3
4
5
1. Service port
2. Cap
3. Hexagon hole
4. Shaft
5. Seal
Torque wrench
Spanner
Piping union
Flare nut
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...