![background image](http://html1.mh-extra.com/html/daikin/reyq96mtju/reyq96mtju_design-installation-and-testing-instruction_4175824055.webp)
Si39-406
Installation
General Information
49
• If converging multiple drain pipes, install according to the procedure shown below.
Select converging drain pipes whose gauge is suitable for the operating capacity of
the unit.
(2) After piping work is finished, check drainage flows smoothly.
• Open the water inlet lid, add approximately
34 oz. (1000 cc) of water gradually and check drainage flow.
T-joint converging drain pipes
≥
3 15/16"
3P086156-3A-9
Open
Water inlet
Portable pump
Water inlet lid
Refrigerant pipes
Close
Bucket
Drain outlet for maintenance
(with rubber plug)
Note: Use this outlet to drain water from the drain pan.
Adding water from
inspection opening
[ WHEN ELECTRIC WIRING WORK IS FINISHED ]
•
Check drainage flow during COOL running, explained under “TEST OPERATION.”
[ WHEN ELECTRIC WIRING WORK IS NOT FINISHED ]
Remove the electric parts box lid, connect a power supply and
remote controller to the terminals.
(Refer to the “Installation Manuals”)
Next, press the inspection/test operation button “
” on the
remote controller. The unit will engage the test operation mode.
Press the operation mode selector button “
” until selecting FAN
OPERATION “
”. Then, press the ON/OFF button “
”. The
indoor unit fan and drain pump will start up. Check that the water
has drained from the unit. Press “
” to go back to the first mode.
You can check whether drainage is satisfactory or not by removing the access opening lid and checking the
water level of the drain pan through the access opening.
Be careful when doing so because the fan is turning at the same time.
TEST
TEST
3P086156-3A-10
L
2
L
1
Electric parts box
208 – 230V single
phase power supply.
Indoor
PC board
L
2
L
1
Power supply
terminal block
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...